350 Fault tracing
A582
Auxiliary fan not
running
Programmable warning:
An auxiliary cooling fan
(connected to the fan
connectors on the control unit)
is stuck or disconnected.
The auxiliary code identifies the fan (
1:
Auxiliary fan 1,
2:
Auxiliary fan 2).
Make sure the front cover of the drive
module is in place and tightened.
Check auxiliary fan(s) and connection(s).
Replace faulty fan.
A5A0
Drive interlock
Programmable warning:
Drive interlock function is
active, i.e. safety circuit
signal(s) connected to
connector XSTO is lost.
Check safety circuit connections. For
more information, see appropriate drive
hardware manual and description of
parameter
(page
).
A5EA Measurement circuit
temperature
Problem with internal
temperature measurement of
the drive.
Check the auxiliary code (format XXXY
YYZZ). “Y YY” specifies through which
BCU control unit channel the fault was
received (“0 00” with a ZCU control unit).
“ZZ” specifies the location:
With control program version 2.8x and
later:
1:
U-phase IGBT,
2:
V-phase IGBT,
3:
W-phase IGBT,
4:
Power supply
board,
5:
Power unit xINT board,
6:
Brake chopper,
7:
Air inlet (TEMP3,
X10),
8:
du/dt filter (TEMP2, X7),
9:
TEMP1 (X6).
With control program version up to and
including 2.7x:
1:
U-phase IGBT,
2:
V-phase IGBT,
3:
W-phase IGBT,
4:
Power unit INT board,
5:
Brake
chopper,
6:
Air inlet,
7:
Power supply
board,
8:
du/dt filter,
FAh:
Air in temp.
A5EB PU board powerfail
Power unit power supply
failure.
Contact your local ABB representative.
A5EC PU communication
internal
Communication errors
detected between the drive
control unit and the power unit.
Check the connections between the drive
control unit and the power unit.
A5ED Measurement circuit
ADC
Problem with measurement
circuit of power unit (analog to
digital converter)
Contact your local ABB representative.
A5EE Measurement circuit
DFF
Problem with current or voltage
measurement of power unit
Contact your local ABB representative.
A5EF
PU state feedback
State feedback from output
phases does not match control
signals.
Contact your local ABB representative.
A5F0
Charging feedback
Charging in progress
Informative warning. Wait until charging
finishes before starting the inverter unit.
A5F3
Switching frequency
below requested
Adequate motor control at
requested output frequency
cannot be reached because of
limited switching frequency
(eg. by parameter
Informative warning.
A5F4
Control unit battery
The battery of the control unit
is low.
Replace control unit battery.
This warning can be suppressed using
parameter
.
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...