Technical data
86
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 4000 m (13123 ft) above
sea level. [See also section
.]
-
-
Air temperature
-10 to +55°C (14 to 131°F).
No frost allowed. See section
on page
-40 to +70°C (-40 to +158°F) -40 to +70°C (-40 to +158°F)
Relative humidity
0 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
According to IEC 60721-3-3:
Chemical gases: Class 3C2
Solid particles: Class 3S2
The drive must be installed in
clean air according to
enclosure classification.
Cooling air must be clean,
free from corrosive materials
and electrically conductive
dust.
According to IEC 60721-3-1:
Chemical cases: Class 1C2
Solid particles: Class 1S2
According to IEC 60721-3-2:
Chemical cases: Class 2C2
Solid particles: Class 2S2
Sinusoidal vibration
(IEC 60721-3-3)
Tested according to
IEC 60721-3-3, mechanical
conditions: Class 3M4
2…9 Hz: 3.0 mm (0.12”)
9…200 Hz: 10 m/s
2
(33 ft/s
2
)
–
–
Shock
(IEC 60068-2-27, ISTA 1A)
–
According to ISTA 1A.
Max. 100 m/s
2
(330 ft/s
2
),
11 ms
According to ISTA 1A.
Max. 100 m/s
2
(330 ft/s
2
),
11 ms
Free fall
Not allowed
76 cm (30”)
76 cm (30”)
Materials
Drive enclosure
• PC/ABS, colour NCS 1502-Y (RAL 9002 / PMS 420 C)
• hot-dip zinc coated steel sheet
• extruded aluminium AlSi.
Packaging
Corrugated cardboard, PP bands.
Disposal
The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are marked
with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors contain electrolyte, which is classified as
hazardous waste within the EU. They must be removed and handled according to local
regulations.
For further information on environmental aspects and more detailed recycling instructions,
please contact your local ABB distributor.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Hardware Manual ACS850 04 Drive Modules 1 1 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 32: ...Planning the cabinet assembly 32...
Page 38: ...Mechanical installation 38...
Page 48: ...Planning the electrical installation 48...
Page 50: ...Electrical installation 50 1 2 3 4 5...
Page 68: ...Electrical installation 68...
Page 76: ...Maintenance 76...
Page 102: ...du dt and common mode filtering 102...
Page 108: ...Dimension drawings 108 Frame size A...
Page 109: ...Dimension drawings 109 Frame size B...
Page 110: ...Dimension drawings 110 Frame size C...
Page 111: ...Dimension drawings 111 Frame size D...
Page 113: ...Dimension drawings 113 EMC filters type JFI x1 JFI A1...
Page 114: ...Dimension drawings 114 JFI B1...
Page 115: ...Dimension drawings 115 EMC filters type JFI 0x...
Page 117: ...Dimension drawings 117 Braking resistors type JBR xx...