Planning the electrical installation
40
• a circuit breaker suitable for isolation in accordance with EN 60947-2.
Other regions
The disconnecting means must conform to the applicable safety regulations.
Thermal overload and short circuit protection
Thermal overload protection
The drive protects itself and the input and motor cables against thermal overload
when the cables are dimensioned according to the nominal current of the drive. No
additional thermal protection devices are needed.
WARNING!
If the drive is connected to multiple motors, a separate thermal overload
switch or a circuit breaker must be used for protecting each cable and motor. These
devices may require a separate fuse to cut off the short-circuit current.
Protection against short-circuit in motor cable
The drive protects the motor cable and the motor in a short-circuit situation when the
motor cable is dimensioned according to the nominal current of the drive. No
additional protection devices are needed.
Protection against short-circuit in the supply cable or the drive
Protect the supply cable with fuses or circuit breakers. Fuse recommendations are
given in the chapter
When placed at the distribution board, standard
IEC gG fuses or UL type T fuses will protect the input cable in short-circuit situations,
restrict drive damage and prevent damage to adjoining equipment in case of a short
circuit inside the drive.
Operating time of the fuses and circuit breakers
Check that the operating time of the fuse is below 0.5 seconds.
The operating
time depends on the type, the supply network impedance, and the cross-sectional
area, material and length of the supply cable. US fuses must be of the “non-time
delay” type.
Circuit breakers
The protective characteristics of circuit breakers depend on the supply voltage as
well as the type and construction of the breakers. There are also limitations
pertaining to the short-circuit capacity of the supply network. Your local ABB
representative can help you in selecting the breaker type when the supply network
characteristics are known.
Motor thermal protection
According to regulations, the motor must be protected against thermal overload and
the current must be switched off when overloading is detected. The drive includes a
motor thermal protection function that protects the motor and switches off the current
when necessary. Depending on a drive parameter value, the function either monitors
Summary of Contents for ACS850 series
Page 1: ...ACS850 Hardware Manual ACS850 04 Drive Modules 1 1 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 32: ...Planning the cabinet assembly 32...
Page 38: ...Mechanical installation 38...
Page 48: ...Planning the electrical installation 48...
Page 50: ...Electrical installation 50 1 2 3 4 5...
Page 68: ...Electrical installation 68...
Page 76: ...Maintenance 76...
Page 102: ...du dt and common mode filtering 102...
Page 108: ...Dimension drawings 108 Frame size A...
Page 109: ...Dimension drawings 109 Frame size B...
Page 110: ...Dimension drawings 110 Frame size C...
Page 111: ...Dimension drawings 111 Frame size D...
Page 113: ...Dimension drawings 113 EMC filters type JFI x1 JFI A1...
Page 114: ...Dimension drawings 114 JFI B1...
Page 115: ...Dimension drawings 115 EMC filters type JFI 0x...
Page 117: ...Dimension drawings 117 Braking resistors type JBR xx...