Technical data
79
Derating
The continuous output currents stated above must be derated if any of the following conditions apply:
• the ambient temperature e40 °C (+104°F)
• the drive is installed higher than 1000 m above sea level.
Note:
The final derating factor is a multiplication of all applicable derating factors.
Ambient temperature derating
In the temperature range +40…55 °C (+104…131 °F), the rated output current is derated by 1% for
every added 1 °C (1.8 °F) as follows:
Altitude derating
At altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool.
Note:
If the installation site is higher than 2000 m (6600 ft) above sea level, connection of the drive to
an ungrounded (IT) or corner-grounded delta network is not allowed.
Ambient temperature
Derating factor
1.00
0.85
+40 °C
+55 °C
+104 °F
+131 °F
Summary of Contents for ACS850 series
Page 1: ...ACS850 Hardware Manual ACS850 04 Drive Modules 1 1 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 32: ...Planning the cabinet assembly 32...
Page 38: ...Mechanical installation 38...
Page 48: ...Planning the electrical installation 48...
Page 50: ...Electrical installation 50 1 2 3 4 5...
Page 68: ...Electrical installation 68...
Page 76: ...Maintenance 76...
Page 102: ...du dt and common mode filtering 102...
Page 108: ...Dimension drawings 108 Frame size A...
Page 109: ...Dimension drawings 109 Frame size B...
Page 110: ...Dimension drawings 110 Frame size C...
Page 111: ...Dimension drawings 111 Frame size D...
Page 113: ...Dimension drawings 113 EMC filters type JFI x1 JFI A1...
Page 114: ...Dimension drawings 114 JFI B1...
Page 115: ...Dimension drawings 115 EMC filters type JFI 0x...
Page 117: ...Dimension drawings 117 Braking resistors type JBR xx...