ELECTRICAL INSTALLATION
PRODUCT
ACS1000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS213400 E01
REV.
J
LANG.
en
PAGE
7.5. Cable entries
The cables can be entered through the roof or the floor of the cabinet.
The cabinet is equipped with one of the following cable entries:
–
Cable entry with EMC plates
–
Cable entry with sealing modules, type 1
–
Cable entry with sealing modules, type 2
–
Cable entry with cable glands
For information on location and dimensions, see “Appendix C
-
Mechanical
drawings”.
7.5.1. Cable entry with EMC plates
–
Usage:
•
Power cables, ground cables and bonding conductors
•
Auxiliary power cables and control cables
–
Included in delivery:
galvanized plate with net-like EMC sleeves (1 in Fig. 7
and sealing grommets (2)
Figure 7
-
2 EMC plate example
1) EMC sleeves
2) Sealing grommets
Ø45 mm
1.5 mm
1
2