POWER ELECTRONICS AND CABINET FEATURES
PRODUCT
ACS1000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS213400 E01
REV.
J
LANG.
en
PAGE
3.6. Door locking system
To ensure safety and to prevent the doors being opened unintentionally, all doors
are lockable. The doors of compartments where medium voltages are present
during operation (2 and 3 in Fig. 3
14) are electro-mechanically secured.
Additionally, the doors of the medium voltage compartments have locks with
different inserts than the control compartment door. The different lock inserts
ensure that these doors can only be opened by personnel authorized to do so.
Figure 3
-
14 Door locks
For more information, see
Section 11.6.2 De-energizing the drive locally
3.6.1. Optional cabinets
If medium voltages are present in an optional cabinet during operation (eg,
braking chopper and output disconnector), the door is secured by an electro-
mechanical lock as well as a door monitoring switch. If the cabinet is UL certified,
the door is further secured with extra screws. The lock and the switch release the
door after the DC link of the drive has discharged and the drive has been grounded.
1) Door of control compartment: lockable
• Partition of terminal compartment behind
control compartment: bolted
2) Door of DC-link and filter compartment:
electro-mechanically locked
• Door cannot be opened when the drive
is energized.
3) Door of rectifier and inverter compartment:
electro-mechanically locked
• Door cannot be opened when the drive
is energized.
4) Door of water cooling compartment:
lockable
1
2
3
4