MECHANICAL INSTALLATION
PRODUCT
ACS1000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS213400 E01
REV.
J
LANG.
en
PAGE
6.3.3. Fire protection
–
To prevent fire spreading into the drive, apply suitable fire protection
measures
6.3.4. Cable duct material
–
Use non-flammable material with non-abrasive surface.
–
To prevent dust, humidity and animals entering the cabinet, protect the cable
entries.
6.4. Preparing the floor
Condition of the floor:
–
Must support the weight of the cabinet
–
Overall incline across 5 m must not exceed 5 mm
–
Even
–
Non-flammable, smooth and non- abrasive
–
Protected against humidity diffusion
6.5. Fixing the cabinet to the floor
IMPORTANT!
If the doors of medium voltage compartments cannot be opened,
contact the ABB service organization.
Required layout drawings
Refer to the relevant layout drawing for detailed instructions on how to fix the
cabinet to the floor:
–
Standard cabinet base fixation: “Fixing & Lifting details ACS1000W”
(3BHS853483 E01)
–
Marine cabinet base fixation: “Fixing & Lifting details ACS1000W Marine”
(3BHS853483 E02)
–
Marine/seismic cabinet base and roof fixation: “Fixing & Lifting details
ACS1000W Seismic” (3BHS853483 E03)