9.7.2. Starting the drive remotely
When the drive is operated from remote through a higher-level control system or
an operator control desk, follow the instructions in the appropriate manuals.
9.7.3. Starting the drive locally
1.
Enable the local control mode of the drive.
2.
Check that no alarm or fault messages are displayed on the CDP control panel.
•
If a fault message is displayed on the CDP control panel, reset the fault.
•
If a fault cannot be reset, it must be rectified by the responsible personnel.
When no alarms and faults are present and the drive is ready, the CDP control
panel displays
RdyForMCBOn
:
3.
Press the
MAIN SUPPLY ON
push button on the control compartment door to
close the MCB and charge the DC link.
The push button lights up and the status line of the CDP control panel changes
to
Charging
.
LOC
REM
RESET
1 L ->
0.0 rpm
Status
RdyforMCBon
MotorSpeed 0.00
rpm
Power
0.0%
1 L ->
0.0 rpm
Status
Charging
MotorSpeed 0.00
rpm
Power
0.0 %