Start-up Guide

6

 

Standard Application Program

7 –  STARTING THE DRIVE THROUGH THE I/O INTERFACE

As default the external start/stop signal is read from the 
digital input DI1, and the external speed reference from the 
analogue input AI1.

Starting through a digital input:

• Press the 

LOC/REM key to change to external control 

(no L visible on the first row of the panel display). 

• Switch on digital input DI1. 

Drive starts. The motor is accelerated to a speed 
determined by the voltage level of analogue input AI1.

Valid if the factory macro is 
selected. See Parameter 
99.02 APPLICATION MACRO.

8 – STOPPING THE MOTOR

Stopping when in local control: Press 

Stopping when in external control: Switch off digital input 
DI1.

Valid if the factory macro is 
selected. See Parameter 
99.02 APPLICATION MACRO.

Press the 

LOC/REM key to change between local and 

external control.

START-UP PROCEDURE

Summary of Contents for ACS 600

Page 1: ...Application Program 5 x ACS 600 Start up Guide This manual includes ACS 600 initialisation using the Control Panel First start Rotation direction check Start through a digital input Speed control usi...

Page 2: ...his Guide describes the basic start up procedure of the ACS 600 frequency converter equipped with the Standard Application Program 5 x See the LUPZDUH 0DQXDO IRU 6 6WDQGDUG SSOLFDWLRQ 3URJUDP for more...

Page 3: ...re the start up procedure See the installation checklist from the appropriate hardware installation manual Check that starting the motor does not cause any danger It is recommended having the driven e...

Page 4: ...given above The default value FACTORY is suitable in most cases A detailed description of the Application Macros is included in Firmware Manual Select the motor control mode The general parameter set...

Page 5: ...general parameter setting procedure is given on Page 2 Allowed range 1 6 I2hd 2 I2hd of ACS 600 Nominal frequency The general parameter setting procedure is given on Page 2 Range 8 300 Hz Nominal spee...

Page 6: ...ro speed Operation at torque range above the motor nominal torque within wide speed range and without any pulse encoder i e without any measured speed feedback is required See the Firmware Manual for...

Page 7: ...otor connection box Verify your work by applying mains power and repeating the check as described above 6 SPEED LIMITS AND ACCELERATION DECELERATION TIMES Set the minimum speed The general parameter s...

Page 8: ...on the first row of the panel display Switch on digital input DI1 Drive starts The motor is accelerated to a speed determined by the voltage level of analogue input AI1 Valid if the factory macro is s...

Page 9: ......

Page 10: ...ABB Industry Oy Drives P O Box 184 FIN 00381 HELSINKI FINLAND Telephone 358 10 22 2000 Telefax 358 10 22 22681 3BFE 64049224 R0125 EFFECTIVE 26 08 1998 EN...

Reviews: