Start-up Guide
Standard Application Program
3
Enter the motor data from the motor nameplate.
Note: Set the motor data exactly the same as on the motor
nameplate. For example, if the motor nominal speed is
1440 rpm on the nameplate, setting the value of Parameter
99.08 MOTOR NOM SPEED to 1500 rpm results in wrong
operation of the drive.
Nominal voltage. The general parameter setting procedure
is given on Page 2.
Allowed range: 1/2 ·
U
N
... 2 ·
U
N
of ACS 600. (
U
N
refers to the highest
voltage in each of the nominal voltage ranges: 415 VAC for 400 VAC
units, 500 VAC for 500 VAC units and 690 VAC for 600 VAC units.)
Nominal current. The general parameter setting procedure
is given on Page 2.
Allowed range: 1/6 ·
I
2hd
... 2 ·
I
2hd
of ACS 600
Nominal frequency. The general parameter setting
procedure is given on Page 2.
Range: 8 ... 300 Hz
Nominal speed. The general parameter setting procedure
is given on Page 2.
Range: 1 ... 18000 rpm
START-UP PROCEDURE
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C3
6312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz
kW
r/min
A
cos
IA/IN t E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
380 V
Mains
Voltage
1 -> 0.0 rpm O
99 START-UP DATA
05 MOTOR NOM VOLTAGE
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
06 MOTOR NOM CURRENT
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
07 MOTOR NOM FREQ
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
08 MOTOR NOM SPEED
[ ]
Summary of Contents for ACS 600
Page 9: ......