background image

Start-up Guide

2

 

Standard Application Program

3 – START-UP DATA ENTERING (Parameter Group 99)

Select the language. The general parameter setting 
procedure is given below.

The general parameter setting procedure:

• Press 

PAR to select parameter mode.

• Press 

 or 

 to scroll Parameter Groups (10 to 99).

• Press 

 or 

 to scroll parameters within the 

Parameter Group.

• Select a new value by 

ENTER (brackets appear around 

the parameter value) and 

 or 

. (Fast change by 

 

or .)

• Press 

ENTER 

to accept the new value (brackets 

disappear).

Select the Application Macro. The general parameter 
setting procedure is given above.

The default value FACTORY is suitable in most cases. A detailed 
description of the Application Macros is included in 

Firmware Manual.

Select the motor control mode. The general parameter 
setting procedure is given above.

DTC is suitable in most cases. The SCALAR control mode is 
recommended

• for multimotor drives when the number of motors connected to the 

ACS 600 is variable. 

• when the nominal current of the motor is less than 1/6 of the nominal 

current of the inverter.

• when the inverter is used for test purposes with no motor connected.

START-UP PROCEDURE

 1   ->  0.0 rpm   O

99 START-UP DATA 

01 LANGUAGE

ENGLISH

 1   ->  0.0 rpm   O

99 START-UP DATA 

01 LANGUAGE

 [ENGLISH]

 1   ->  0.0 rpm   O

99 START-UP DATA 

02 APPLICATION MACRO

 [ ]

 1   ->   0.0 rpm  O

99 START-UP DATA 
04 MOTOR CTRL MODE

 [DTC]

Summary of Contents for ACS 600

Page 1: ...Application Program 5 x ACS 600 Start up Guide This manual includes ACS 600 initialisation using the Control Panel First start Rotation direction check Start through a digital input Speed control usi...

Page 2: ...his Guide describes the basic start up procedure of the ACS 600 frequency converter equipped with the Standard Application Program 5 x See the LUPZDUH 0DQXDO IRU 6 6WDQGDUG SSOLFDWLRQ 3URJUDP for more...

Page 3: ...re the start up procedure See the installation checklist from the appropriate hardware installation manual Check that starting the motor does not cause any danger It is recommended having the driven e...

Page 4: ...given above The default value FACTORY is suitable in most cases A detailed description of the Application Macros is included in Firmware Manual Select the motor control mode The general parameter set...

Page 5: ...general parameter setting procedure is given on Page 2 Allowed range 1 6 I2hd 2 I2hd of ACS 600 Nominal frequency The general parameter setting procedure is given on Page 2 Range 8 300 Hz Nominal spee...

Page 6: ...ro speed Operation at torque range above the motor nominal torque within wide speed range and without any pulse encoder i e without any measured speed feedback is required See the Firmware Manual for...

Page 7: ...otor connection box Verify your work by applying mains power and repeating the check as described above 6 SPEED LIMITS AND ACCELERATION DECELERATION TIMES Set the minimum speed The general parameter s...

Page 8: ...on the first row of the panel display Switch on digital input DI1 Drive starts The motor is accelerated to a speed determined by the voltage level of analogue input AI1 Valid if the factory macro is s...

Page 9: ......

Page 10: ...ABB Industry Oy Drives P O Box 184 FIN 00381 HELSINKI FINLAND Telephone 358 10 22 2000 Telefax 358 10 22 22681 3BFE 64049224 R0125 EFFECTIVE 26 08 1998 EN...

Reviews: