Start-up Guide

Standard Application Program

5

5 – ROTATION DIRECTION OF THE MOTOR

Check the rotation direction of the motor.

• Press 

ACT to get the status row visible. 

• Increase the speed reference from zero to a small value 

by pressing 

REF and then 

 or 

 (

 or 

). 

• Press 

 (Start) to start the motor. 

• Check that the motor is running in the desired direction.

• Stop the motor by pressing 

.

To change the rotation direction of the motor:

• Disconnect mains power from the ACx 600, and wait 5 minutes for the 

intermediate circuit capacitors to discharge. Measure the voltage 
between each input terminal (U1, V1 and W1) and earth with a 
multimeter to ensure that the frequency converter is discharged.

• Exchange the position of two motor cable phase conductors at the 

motor terminals or at the motor connection box.

• Verify your work by applying mains power and repeating the check as 

described above.

6 – SPEED LIMITS AND ACCELERATION/DECELERATION TIMES

Set the minimum speed. The general parameter setting 
procedure is given on Page 2.

Set the maximum speed. The general parameter setting 
procedure is given on Page 2.

Set the acceleration time 1. The general parameter setting 
procedure is given on Page 2.

Note: Check also acceleration time 2, if two acceleration 
times will be used in the application.

Set the deceleration time 1. The general parameter setting 
procedure is given on Page 2.

Note: Set also deceleration time 2, if two deceleration 
times will be used in the application.

START-UP PROCEDURE

 1  L->[xxx] rpm   I

FREQ        xxx Hz

CURRENT      xx A

POWER        xx %

forward 
direction

reverse     
direction

 1  L->  0.0 rpm   O

20 LIMITS 
01 MINIMUM SPEED

[ ]

 1  L->   0.0 rpm  O

20 LIMITS 

02 MAXIMUM SPEED

 [ ]

 1  L->   0.0 rpm  O

22 ACCEL/DECEL 
02 ACCELER TIME 1

 [ ]

 1  L->   0.0 rpm  O

22 ACCEL/DECEL 
03 DECELER TIME 1

 [ ]

Summary of Contents for ACS 600

Page 1: ...Application Program 5 x ACS 600 Start up Guide This manual includes ACS 600 initialisation using the Control Panel First start Rotation direction check Start through a digital input Speed control usi...

Page 2: ...his Guide describes the basic start up procedure of the ACS 600 frequency converter equipped with the Standard Application Program 5 x See the LUPZDUH 0DQXDO IRU 6 6WDQGDUG SSOLFDWLRQ 3URJUDP for more...

Page 3: ...re the start up procedure See the installation checklist from the appropriate hardware installation manual Check that starting the motor does not cause any danger It is recommended having the driven e...

Page 4: ...given above The default value FACTORY is suitable in most cases A detailed description of the Application Macros is included in Firmware Manual Select the motor control mode The general parameter set...

Page 5: ...general parameter setting procedure is given on Page 2 Allowed range 1 6 I2hd 2 I2hd of ACS 600 Nominal frequency The general parameter setting procedure is given on Page 2 Range 8 300 Hz Nominal spee...

Page 6: ...ro speed Operation at torque range above the motor nominal torque within wide speed range and without any pulse encoder i e without any measured speed feedback is required See the Firmware Manual for...

Page 7: ...otor connection box Verify your work by applying mains power and repeating the check as described above 6 SPEED LIMITS AND ACCELERATION DECELERATION TIMES Set the minimum speed The general parameter s...

Page 8: ...on the first row of the panel display Switch on digital input DI1 Drive starts The motor is accelerated to a speed determined by the voltage level of analogue input AI1 Valid if the factory macro is s...

Page 9: ......

Page 10: ...ABB Industry Oy Drives P O Box 184 FIN 00381 HELSINKI FINLAND Telephone 358 10 22 2000 Telefax 358 10 22 22681 3BFE 64049224 R0125 EFFECTIVE 26 08 1998 EN...

Reviews: