Start-up Guide

4

 

Standard Application Program

Nominal power. The general parameter setting procedure is 
given on Page 2.

Range: 0... 9000 kW

When the motor data has been entered a warning appears. 
It indicates that the motor parameters have been set, and 
the ACS  600 is ready to start the motor identification 
(ID magnetisation or ID Run).

Select the motor identification. The general parameter 
setting procedure is given on Page 2.

The default value NO is suitable for most applications. It is applied in this 
basic start-up procedure.

The ID Run (STANDARD or REDUCED) should be selected instead if:

• Operation point is near zero speed.

• Operation at torque range above the motor nominal torque within wide 

speed range and without any pulse encoder (i.e. without any 
measured speed feedback) is required.

See the 

Firmware Manual for the ID Run procedure.

4 – IDENTIFICATION MAGNETISATION

with Motor ID Run selection NO

Press the 

LOC/REM key to change to local control (L 

shown on the first row).

Press the 

 to start the magnetisation. The motor is 

magnetised at zero speed for 20 to 60 s. Two warnings are 
displayed:

• The upper warning is displayed while the magnetisation 

is on. 

• The lower warning is displayed after the magnetisation is 

completed.

START-UP PROCEDURE

 1   ->  0.0 rpm   O

99 START-UP DATA 
09 MOTOR NOM POWER

 [ ]

 1   ->  0.0 rpm   O

** WARNING **

ID MAGN REQ

 1   ->   0.0 rpm  O

99 START-UP DATA 

10 MOTOR ID RUN
 [NO]

 1  L->  0.0 rpm   I

** WARNING **

ID MAGN

 1  L->  0.0 rpm   O

** WARNING **

ID DONE

Summary of Contents for ACS 600

Page 1: ...Application Program 5 x ACS 600 Start up Guide This manual includes ACS 600 initialisation using the Control Panel First start Rotation direction check Start through a digital input Speed control usi...

Page 2: ...his Guide describes the basic start up procedure of the ACS 600 frequency converter equipped with the Standard Application Program 5 x See the LUPZDUH 0DQXDO IRU 6 6WDQGDUG SSOLFDWLRQ 3URJUDP for more...

Page 3: ...re the start up procedure See the installation checklist from the appropriate hardware installation manual Check that starting the motor does not cause any danger It is recommended having the driven e...

Page 4: ...given above The default value FACTORY is suitable in most cases A detailed description of the Application Macros is included in Firmware Manual Select the motor control mode The general parameter set...

Page 5: ...general parameter setting procedure is given on Page 2 Allowed range 1 6 I2hd 2 I2hd of ACS 600 Nominal frequency The general parameter setting procedure is given on Page 2 Range 8 300 Hz Nominal spee...

Page 6: ...ro speed Operation at torque range above the motor nominal torque within wide speed range and without any pulse encoder i e without any measured speed feedback is required See the Firmware Manual for...

Page 7: ...otor connection box Verify your work by applying mains power and repeating the check as described above 6 SPEED LIMITS AND ACCELERATION DECELERATION TIMES Set the minimum speed The general parameter s...

Page 8: ...on the first row of the panel display Switch on digital input DI1 Drive starts The motor is accelerated to a speed determined by the voltage level of analogue input AI1 Valid if the factory macro is s...

Page 9: ......

Page 10: ...ABB Industry Oy Drives P O Box 184 FIN 00381 HELSINKI FINLAND Telephone 358 10 22 2000 Telefax 358 10 22 22681 3BFE 64049224 R0125 EFFECTIVE 26 08 1998 EN...

Reviews: