![ABB ACS 600 Series Hardware Manual Download Page 75](http://html1.mh-extra.com/html/abb/acs-600-series/acs-600-series_hardware-manual_3379279075.webp)
Appendix C – IEC Installation
ACS/ACC/ACP 604/607 Drives
ACx=ACS/ACC/ACP
C-5
Mains, Motor and
Control Cable
Connection
A view of the recommended earthing, mains and motor cable
connections of the ACx 607 is presented below. F denotes a 360
degrees earthing.
ACx 607
Frequency
Converter
U1
V1
W1
3
~
Motor
U2
V2
W2
ACx 604
Converter Unit
UDC+
UDC-
PE
Line Options
U1
W1
V1
Max 6 control cables
F
1)
2)
1) used if the conductivity of the cable screen is <
50 % of the conductivity of the phase conductor.
2) used if the PE rail of ACx 607 is not earthed via
separate PE conductor or via cable screen.
3) used only if local safety regulations do not accept
earthing of the ACx 607 and the motor merely
through the cable screen.
Note: Connecting the fourth conductor of the
cable at the motor increases bearing currents,
thus causing extra wear.
4) The NIOC/NIOCP board is located inside the
module in ACx 604 deliveries.
F
U1
W1
V1
L1 L2 L3 PE
T41
X2
F
3)
For minimum radio frequency
interference (RFI) at the motor
end, earth the cable screen 360
degrees at the lead-through or
earth the cable by twisting the
screen (flattened width > 1/5 ·
length).
du/dt Filter
EMC Line Filter
(option)
NIOC/ NIOCP
NAMC
4)
NIOC/ NIOCP
NAMC
Summary of Contents for ACS 600 Series
Page 2: ......
Page 4: ......
Page 16: ...xiv ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 20: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 38: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 72: ...Appendix B ACx 607 Dimensional Drawings B 2 ACx ACX ACC ACP ACS ACC ACP 604 607 Drives ...
Page 81: ......