Appendix A – ACS/ACC/ACP 604/607 Technical Data
A-18
ACx=ACS/ACC/ACP
ACS/ACC/ACP 604/607 Drives
Enclosures, Space
Requirements
The cabinets, degrees of protection and free space requirements of
ACx 600 types are given below.
1) ACx 604-0100-3, -0120-3, -0120-5, -0140-5, -0100-6, -0120-6
2)
ACx 604-0140-3 to -0320-3 & -0170-5 to -0400-5, -0140-6 to -0400-6
3)
not for frame sizes 2xR8 and 2xR9
4)
The degrees of protection is specified by listing the IEC standard IP (Ingress Protection) number. The first digit of the IP number specifies
the protection against solid objects and dirt. The second digit specifies the protection against liquids. IP 00 is an open chassis. NEMA 1
enclosures are comparable to approximately IP 20 to IP 33. NEMA 3R enclosures are comparable to IP 32. NEMA 12 and NEMA 13
enclosures are comparable to IP 54 to IP 65. NEMA 4 enclosures are comparable to IP 65 or IP 66.
ACx 600 Type
Enclosure
Degree of
Protection
5)
Space above
Space below
Space on
left/right
Space in
front/back
mm
in
mm
in
mm
in
mm
in
604
2)
frame R7
IP 22
300
12
300
12
50/50
2/2
20/0
0.8/0
604
3)
frames R8 and R9
IP 00
400
16
0
0
0/50
0/2
100/0
4/0
607
Drives-MNS cabinet
IP 21
4)
/22
IP 42/54
200
8
0
0
0
0
200/0
8/0
First digit of IP number (protection against solid objects)
Second digit of IP number (protection against liquids)
0
Not protected
Not protected
1
Protected against solid objects larger than 50 mm (2 in.) dia.
Protected against dripping water
2
Protected against solid objects larger than 12 mm (1/2 in.) dia.
Protected against downward sprays of water up to 15 degrees
from vertical.
3
Protected against solid objects larger than 2.5 mm (0.1 in.) dia.
Protected against downward sprays of water up to 60 degrees
from vertical.
4
Protected against solid objects larger than 1.0 mm (0.04 in.) dia. Protected against light sprays or splashing water from all
directions - water shall not enter the enclosure in harmful
quantities.
5
Dust protected - dust shall not enter the enclosure in sufficient
quantity to interfere with satisfactory operation of equipment.
Protected against low pressure sprays of water from all directions
- water shall not enter the enclosure in harmful quantities.
6
Dust tight
Protected against heavy seas on shipdecks or strong sprays of
water from all directions - water shall not enter the enclosure in
harmful quantities.
Space requirement for the door opening
700 mm (27.6 in.) (2 x R8 and 2 x R9)
800 mm (31.5 in.) (R7, R8 and R9)
Summary of Contents for ACS 600 Series
Page 2: ......
Page 4: ......
Page 16: ...xiv ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 20: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 38: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 72: ...Appendix B ACx 607 Dimensional Drawings B 2 ACx ACX ACC ACP ACS ACC ACP 604 607 Drives ...
Page 81: ......