ACS/ACC/ACP 604/607 Drives
ACx=ACS/ACC/ACP
2-1
Chapter 2 – Mechanical Installation
For installation of ACx 604 module in a cabinet refer to a supplement to
this manual:
Converter Module Installation in User-defined Cabinet.
The ACx 607 should be installed in an upright vertical position.
The floor that the unit is installed on should be of non-flammable
material, as smooth as possible, and strong enough to support the
weight of the unit. The maximum allowed deviation from the surface
level must be < 2 mm (0.08 in) measured every 1 m (40in). The
installation site should be leveled (when needed), as the ACx 607 is
not equipped with adjustable feet.
The ACx 607 can be installed on an elevated floor and over a cable
duct. The integrity of the supporting structure must be checked before
the ACx 607 is placed in such a position.
ACx 607 can be installed with its back against a wall. Sufficient room
around the ACx 607 is required to enable cooling air flow, service and
maintenance. Refer to Enclosure Space Requirements in Appendix A
on page A-7. Be sure to also observe all safety requirements of
applicable safety regulations
The wall behind the unit should be of non-flammable material.
Check The Installation
Site
Check the intended installation site to make sure that the environment
is suitable. The service life and performance of the ACx 600 can be
adversely affected if the drive is subjected to unsuitable environmental
conditions. Complete environmental rating specifications are listed in
Appendix A.
If unsuitable conditions are found at the intended installation site,
select a different location, improve the environment at the selected site,
or provide additional protection for the ACx 601.
Installation Site
Checklist
Make sure that the ambient temperature is suitable for the type of
enclosure provided and the output current required. (pages A-3 & A-4
and A-12)
Make sure that the installation site altitude is suitable for the output
current required. (A-12)
Make sure that the ambient air is sufficiently clean and dry or that
the drive is adequately protected from contaminants. (A-12)
Make sure that the enclosure selected is adequate to protect the
drive considering site conditions regarding access by unauthorized
persons, liquids that might be splashed, sprayed or fall on the
enclosure, or any other foreign material that might get into the
Summary of Contents for ACS 600 Series
Page 2: ......
Page 4: ......
Page 16: ...xiv ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 20: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 38: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 72: ...Appendix B ACx 607 Dimensional Drawings B 2 ACx ACX ACC ACP ACS ACC ACP 604 607 Drives ...
Page 81: ......