Appendix A – ACS/ACC/ACP 604/607 Technical Data
A-12
ACx=ACS/ACC/ACP
ACS/ACC/ACP 604/607 Drives
Optional Terminal Block
X2
External connections to optional terminal block X2 for ACS 600
Standard Application Program (Factory Macro) are shown below.
External control connections are different with other application macros
and programs (see
Firmware Manual).
.
AC
S
60
7 I/
O I
nte
rfa
ce
(o
ptio
na
l)
AC
S 60
1/6
04
/60
7
NI
OC
B
oar
d
(A
2)
Programmable I/O
Factory Settings
X2
X21
1
--------
1
VREF
Reference voltage
10 V d.c.
1 k
Ω
<
R
L
< 10 k
Ω
2
--------
2
GND
3
--------
3
AI1+
Speed reference
0(2)... 10 V
R
in
> 200 k
Ω
4
--------
4
AI1-
5
--------
5
AI2+
By default, not in use.
0(4)... 20 mA
, R
in
= 100
Ω
6
--------
6
AI2-
7
--------
7
AI3+
By default, not in use.
0(4)... 20 mA
, R
in
= 100
Ω
8
--------
8
AI3-
9
--------
9
AO1+
Motor speed 0(4)...20 mA
0...motor nom. speed,
R
L
< 700
Ω
10
--------
10
AO1-
11
--------
11
AO2+
Output current
0(4)...20 mA
0...motor nom. current,
R
L
< 700
Ω
12
--------
12
AO2-
X22
13
--------
1
DI1
Stop/Start
14
--------
2
DI2
Forward/Reverse
1)
15
--------
3
DI3
Not used
16
--------
4
DI4
ACCEL/DECEL 1/2
17
--------
5
DI5
Constant speed select
2)
18
--------
6
DI6
Constant speed select
2)
19
--------
7
+24V
+24 V d.c. max. 100 mA
20
--------
8
+24V
21
--------
9
DGND
Digital Ground
X23
22
--------
1
+24 V
Auxiliary voltage output, non-
isolated, 24 V d.c. 250 mA
23
--------
2
GND
X25
24
--------
1
RO11
Relay output 1
Ready
25
--------
2
RO12
26
--------
3
RO13
X26
27
--------
1
RO21
Relay output 2
Running
28
--------
2
RO22
29
--------
3
RO23
X27
30
--------
1
RO31
Relay output 3
Fault (-1)
31
--------
2
RO32
32
--------
3
RO33
=
=
Terminal Block Size
X21, X22, X23, X25, X26, X27:
cables 0.5 to 1.5 mm
2
(#20 to #16 AWG)
X2: cables 0.5 to 2.5 mm
2
(#20 to #14 AWG)
Control Cable Lead-through Size:
Ø: 2 x 3x2...11 mm (0.08 to 0.43”)
Factory settings of application software
selection B (type code):
DI1: Start, DI2: Stop, DI3: Reverse,
DI4: Acc/Dec 2,
DI5,6: Constant speed 1 to 3 select.
1)
Parameter 10.3 must be set to REQUEST.
2)
Operation: 0 = Open, 1 = Closed
Connector X28 for RS 485 connection
Connector X29 for RS 485 connection
DI 5
DI 6
Output
0
0
Set speed through AI 1
1
0
Constant Speed 1
0
1
Constant Speed 2
1
1
Constant Speed 3
1
TRANS
Panel Link Connections
2
GND
3
B-
4
A+
5
GND
Power to Remote Panel
6
+24V
1
TRANS
Panel Link Connections
2
FAULT
3
B-
4
A+
5
GND
Power to Panel
Fault
A
rpm
Summary of Contents for ACS 600 Series
Page 2: ......
Page 4: ......
Page 16: ...xiv ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 20: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 38: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 72: ...Appendix B ACx 607 Dimensional Drawings B 2 ACx ACX ACC ACP ACS ACC ACP 604 607 Drives ...
Page 81: ......