Appendix A – ACS/ACC/ACP 604/607 Technical Data
ACS/ACC/ACP 604/607 Drives
ACx=ACS/ACC/ACP
A-15
NIOC and NIOCP
Board Specifications
Data of the external control connection boards of the ACS 600 product
family are given below.
ACS/ACC/ACP 600
NIOC-01 Board
ACP 600
NIOCP-01 Board
Analog Inputs
The advantage of the
differential analog
input is that the
ground potential of
the device or
transmitter sending
an analog signal can
differ up to ± 15 V
from the ground
potential of the
ACx 600 chassis
without disturbing the
signal. Differential
input also efficiently
attenuates common
mode disturbances
coupled to control
cables.
ACS 600: Two Programmable Differential
Current Inputs: 0 (4) to 20 mA,
R
in
= 100
Ω
ACC 600: Two Differential Current Inputs:
0 to 20 mA,
R
in
= 100
Ω
ACP 600: One Programmable Differential
Current Input: 0 to 20 mA,
R
in
= 100
Ω
ACS/ACP 600: One Programmable
Differential Voltage Input: ACS 600: 0 (2) to
10 V,
R
in
> 200 k
Ω
; ACP 600: 0 to 10 V,
R
in
>
200 k
Ω
ACC 600: One Differential Voltage Input: 0
to 10 V,
R
in
> 200 k
Ω
Common Mode Voltage:
±
15 VDC, max.
Common Mode Rejection Ratio: > 60 dB at
50 Hz
Resolution: 0.1 % (10 bit)
Inaccuracy:
±
0.5% (Full Scale Range) at
77
°
F(25
°C
). Temperature Coefficient:
±
200 ppm/
°
C,(110ppm/
°
F) max.
Input Updating Time: 12 ms (ACS 600),
44 ms (ACC 600), 1 ms (ACP 600)
Two Bipolar Differential Voltage Inputs:
±
10 V,
R
in
= 30 k
Ω
Common Mode Voltage:
±
20 VDC, max.
Common Mode Rejection Ratio: > 60 dB at
50 Hz
Resolution: 0.02 % (12 bit)
Accuracy: 11 bit
Inaccuracy:
±
0.1% (Full Scale Range) at
77
°
F(25
°C
)Temperature Coefficient:
±
100 ppm/
°
C (56ppm/
°
F), max.
Input Updating Time: 1 ms
Constant Voltage
Output
Voltage: 10 VDC ± 0.5% (Full Scale Range) at
77 °F(25
°C
). Temperature Coefficient:
± 100 ppm/°C, max.
Maximum Load: 10 mA
Applicable Potentiometer: 1 k
Ω
to 10 k
Ω
Voltage: ± 10 VDC ± 0.5% (Full Scale Range)
at 77 °F(25
°C
). Temperature Coefficient:
± 100 ppm/°C 56ppm/
°
F), max.
Maximum Load: 10 mA
Applicable Potentiometer: > 1 k
Ω
Auxiliary Power
Output
Voltage: 24 VDC ± 10% Short circuit proof
Maximum Current: 250 mA (130 mA with
NLMD-01 option)
Voltage: 24 VDC ± 10% Short circuit proof
Maximum Current: 250 mA
Analog Outputs
ACS/ACC 600: Two Programmable Current
Outputs: 0 (4) to 20 mA,
R
L
< 700
Ω
ACP 600: One Programmable Current
Output: 0 to 20 mA,
R
L
< 700
Ω
Resolution: 0.1 % (10 bit)
Inaccuracy:
±
1% (Full Scale Range) at77 °F
(25
°
C). Temperature Coefficient:
±
200 ppm/
°
C, max.
Output Updating Time: 24 or 100 ms
(ACS 600), 44 ms (ACC 600), 8 ms (ACP 600)
One Bipolar Programmable Voltage Output:
+ 10 V,
R
L
> 2 k
Ω
Resolution: 0.02% (12 bit)
Accuracy: 10 bit
Inaccuracy:
±
0.1% (Full Scale Range) at77
°F (25
°
C). Temperature Coefficient:
±
200 ppm/
°
C, max.
Output Updating Time: 2 ms
Output Rising Time: 3 ms
Summary of Contents for ACS 600 Series
Page 2: ......
Page 4: ......
Page 16: ...xiv ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 20: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 38: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Page 72: ...Appendix B ACx 607 Dimensional Drawings B 2 ACx ACX ACC ACP ACS ACC ACP 604 607 Drives ...
Page 81: ......