46 Program features
Control interfaces
Programmable analog inputs
The control unit has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V) or current (0/4…20 mA) input with
parameters. Each input can be filtered, inverted and scaled.
Settings
Parameter group
(page
).
Programmable analog outputs
The control unit has two current (0…20 mA) analog outputs. Analog output 1 can be
set as a voltage (0/2…10 V) or current (0/4…20 mA) output with a parameter. Analog
output 2 always uses current. Each output can be filtered, inverted and scaled.
Settings
Parameter group
(page
Programmable digital inputs and outputs
The control unit has six digital inputs.
Digital input DI5 can be used as a frequency input.
Digital input DI6 can used as a thermistor input.
Six digital inputs can be added by using a CHDI-01 115/230 V digital input extension
module and one digital output by using a CMOD-01 multifunction extension module.
Settings
Parameter groups
(page
) and
(page
Programmable frequency input and output
Digital input DI5 can be configured as a frequency input.
A frequency output can be implemented with a CMOD-01 multifunction extension
module.
Settings
Parameter groups
(page
) and
(page
) and
(page
).
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...