128 Parameters
13
Configuration of standard analog outputs.
The source signals of the analog outputs can be overridden
for eg. testing purposes. A forced value parameter is provided
for each analog output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
and
0000h
0000h…FFFFh
Forced values selector for analog outputs AO1 and AO2.
1 = 1
Displays the value of AO1 in mA or V.
This parameter is read-only.
-
0.000…22.000 mA /
0.000…11.000 V
Value of AO1.
1 = 1 mA
Selects a signal to be connected to analog output AO1.
Zero
None. 0
Motor speed used
(page
1
Reserved
2
Output frequency
(page
).
3
Motor current
(page
4
Motor current % of
motor nominal
5
Motor torque
(page
).
6
DC voltage
7
Output power
). 8
Reserved
9
Speed ref ramp in
(page
10
Speed ref ramp out
).
11
Speed ref used
12
Reserved
13
Freq ref used
(page
).
14
Reserved
15
Process PID out
16
Reserved
17…19
Temp sensor 1
excitation
The output is used to feed an excitation current to the
temperature sensor 1, see parameter
(page
).
20
Temp sensor 2
excitation
The output is used to feed an excitation current to the
temperature sensor 2, see parameter
(page
).
21
No.
Name/Value
Description
Def/FbEq16
Bit
Value
0
1 = Force AO1 to value of parameter
. (0 = Normal mode)
1
1 = Force AO2 to value of parameter
. (0 = Normal mode)
2…15
Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...