![ABB ACH550-01 User Manual Download Page 298](http://html.mh-extra.com/html/abb/ach550-01/ach550-01_user-manual_2924298.webp)
286
Parameter listing and descriptions
ACH550 User's Manual
Group 53: EFB PROTOCOL
This group defines set-up variables used for an embedded
fieldbus (EFB) communication protocol. Refer to the
communication protocol documentation for more information on
these parameters.
Code Description
Range
5301
EFB PROTOCOL ID
0…0xFFFF
Contains the identification and program revision of the protocol.
• Format: XXYY, where xx = protocol ID, and YY = program revision.
5302
EFB STATION ID
0…65535
Defines the node address of the RS485 link.
• The node address on each unit must be unique.
5303
EFB BAUD RATE
1.2, 2.4, 4.8, 9.6, 19.2,
Defines the communication speed of
38.4, 57.6, 76.8 kb/s
the RS485 link in kbits per second (kb/s).
1.2 kb/s
2.4 kb/s
4.8 kb/s
9.6 kb/s
19.2 kb/s
38.4 kb/s
57.6 kb/s
76.8 kb/s
5304
EFB PARITY
0…3
Defines the data length parity and stop bits to be used with the RS485
link communication.
• The same settings must be used in all on-line stations.
0 = 8
N
1 – 8 data bits, no parity, one stop bit.
1 = 8
N
2 – 8 data bits, no parity, two stop bits.
2 = 8
E
1 – 8 data bits, even parity, one stop bit.
3 = 8
O
1 – 8 data bits, odd parity, one stop bit.
5305
EFB CTRL PROFILE
0…2
Selects the communication profile used by the EFB protocol.
0 =
ABB
DRIV
LIM
– Operation of the Control Word and Status Word
conforms to ABB Drives Profile, as used in ACS400.
1 =
DCU
PROFILE
– Operation of Control/Status Words conforms to 32-bit
DCU Profile.
2 =
ABB
DRV
FULL
– Operation of Control/Status Words conforms to ABB
Drives Profile, as used in ACS600/800.
5306
EFB OK MESSAGES
0…65535
Contains a count of valid messages received by the drive.
• During normal operation, this counter is increasing constantly.
Summary of Contents for ACH550-01
Page 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Page 10: ...Update Notice 8 ...
Page 12: ......
Page 18: ...6 ACH550 User s Manual ...
Page 50: ...38 Preparing for installation ACH550 User s Manual ...
Page 325: ...313 ACH550 User s Manual ...
Page 358: ...346 ACH550 User s Manual ...
Page 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Page 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Page 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Page 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Page 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Page 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Page 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Page 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Page 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Page 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Page 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Page 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Page 453: ......