RS485 limits and network design
Section 3 Fieldbus Topologies
70
3BDS009029R5001 B
RS485 limits and network design
As described in the PROFIBUS RS485 specification, each bus segment can have a
maximum of 32 active devices. In order to be able to connect a larger number of
PROFIBUS DP devices, it is necessary to segment the bus. The segments are then
interconnected with repeaters which amplify and refresh the data signals. Repeaters
can also be used for galvanic isolation of bus segments or bus sections. Each
repeater allows the PROFIBUS system to be extended by an additional bus segment
with the maximum admissible cable length and the maximum number of fieldbus
devices. Repeaters increase the signal propagation times. This should be taken into
account during planning.
Table 8. General Data PROFIBUS DP
Maximum number of stations
participating in the exchange
of user data
DP: 126 (addresses from 0 .. 125)
Maximum number of stations
per segment including
repeaters
32
Available data transfer rates
in kbit/s
9.6
19.2 45.4
5
93.7
5
187.
5
500
1500
3000
6000
12000
Max. RS485 segment length in
m *
1200
1000 400
200
185 * 120 *
100
Max. spur lines length
Dependent on the data transmission rate.
The use of passive bus
spur lines should be avoided.
Max. fibre optic cable length in
m
44 (plastic),1700 (glass) up to 15000 (PCF)
Max. number of segments
in series
9
According to EN 50170, a maximum of 9 repeaters are allowed
between any two stations.
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M PROFIBUS DP Installation System Version 5 0 5 1...
Page 8: ...Table of Contents 8 3BDS009029R5001 B...
Page 16: ...Released User Manuals and Release Notes About This User Manual 16 3BDS009029R5001 B...
Page 116: ...Updates in Revision Index B 116 3BDS009029R5001 B...
Page 117: ......