Section 2 Transmission Technology
PROFIBUS DP/PA Linking Device LD 800P
3BDS009029R5001 B
41
LD 800P performs the following tasks:
•
Potential separation between the PROFIBUS DP and the PROFIBUS PA
•
Conversion of the RS 485 physical arrangement of the PROFIBUS DP to the
physical arrangement based on IEC 61158-2 of the PROFIBUS PA.
•
Support of all standardized PROFIBUS transmission rates from 45.45 kbit/s up
to 12Mbit/s
•
Automatic detection of transmission rate
•
Fully transparent in the PROFIBUS line
–
No configuration and commissioning
–
Direct access from PROFIBUS DP master to PROFIBUS PA slaves
–
Support of all cyclic and acyclic PROFIBUS protocol services (DP/V1)
–
No restriction in PROFIBUS data volume with full 244 Byte read/write
access to each PA slave
•
Optional PROFIBUS DP line redundancy
•
Power Link Modules integrate bus termination, galvanic isolation and power
supply
•
Powering of PROFIBUS PA segments without additional power supply
•
Optional Power Link Module with intrinsically safe interface [EEx ia] IIC
For more details, please read the LD 800P product documentation.
Figure 8. PROFIBUS DP/PA Linking Device LD 800P