Action registers
Write day profile
configuration
The following table describes the group of registers for configuring a day
profile action:
Function
Byte number Description
Execution time
0 (High byte)
Hour when the action shall be performed.
1 (Low byte)
Minute when the action shall be performed.
Action id
(Both bytes)
Decides the action to perform. See the list of
possible actions below.
Note
–
Both registers in the table above must be written in one operation,
otherwise
the values will not take effect.
Possible actions to perform are activating tariffs and setting or resetting
outputs. The possible values for action id are listed in the table below:
Value
Description
0
Activate tariff 1
...
...
3
Activate tariff 4
100
Set output 1
101
Reset output 1
...
...
106
Set output 4
107
Reset output 4
Follow the steps in the table below to configure the day profiles:
Step
Action
1
Write the number of day profiles to use to the Number of day profiles register.
This is a value between 1 and 16.
2
Write the number of actions to perform for the first day profile to the Number of
actions register. This is a number between 1 and 30.
3
Write the execution time and action id for the first action to perform during the
day to the Action registers.
4
Repeat step 3 for all actions that shall be performed during the day, i.e. the
same number of times as the value written in step 2.
5
Repeat step 2-4 for all day profiles, i.e. the same number of times as the value
written in step 1.
Summary of Contents for A43
Page 1: ...A43 A44 User Manual ...
Page 40: ...Meter Settings A43 A44 40 2CMC48001M0201 User Manual Revision C ...
Page 55: ...Technical Description 2CMC48001M0201 55 A43 A44 Revision C User Manual ...
Page 58: ...Technical Description A43 A44 58 2CMC48001M0201 User Manual Revision C ...
Page 61: ...Technical Description 2CMC48001M0201 61 A43 A44 Revision C User Manual ...
Page 75: ...Technical Description 2CMC48001M0201 75 A43 A44 Revision C User Manual ...
Page 84: ...Measurement Methods A43 A44 84 2CMC48001M0201 User Manual Revision C ...
Page 91: ...Measurement Methods 2CMC48001M0201 91 A43 A44 Revision C User Manual ...
Page 95: ...Measurement Methods 2CMC48001M0201 95 A43 A44 Revision C User Manual ...
Page 102: ...Communication with Modbus A43 A44 102 2CMC48001M0201 User Manual Revision C ...
Page 107: ...Communication with Modbus 2CMC48001M0201 107 A43 A44 Revision C User Manual ...
Page 131: ...Communication with Modbus 2CMC48001M0201 131 A43 A44 Revision C User Manual ...
Page 147: ...Communication with Modbus 2CMC48001M0201 147 A43 A44 Revision C User Manual ...
Page 154: ...Communication with Modbus A43 A44 154 2CMC48001M0201 User Manual Revision C ...
Page 157: ...Communication with Modbus 2CMC48001M0201 157 A43 A44 Revision C User Manual ...
Page 161: ...Communication with Modbus 2CMC48001M0201 161 A43 A44 Revision C User Manual ...
Page 166: ...Communication with Modbus A43 A44 166 2CMC48001M0201 User Manual Revision C ...
Page 180: ...Communication with M Bus A43 A44 180 2CMC48001M0201 User Manual Revision C ...
Page 182: ...Communication with M Bus A43 A44 182 2CMC48001M0201 User Manual Revision C ...
Page 188: ...Communication with M Bus A43 A44 188 2CMC48001M0201 User Manual Revision C ...
Page 195: ...Communication with M Bus 2CMC48001M0201 195 A43 A44 Revision C User Manual ...
Page 254: ...Communication with M Bus A43 A44 254 2CMC48001M0201 User Manual Revision C ...
Page 257: ...Communication with M Bus 2CMC48001M0201 257 A43 A44 Revision C User Manual ...