Communication with Modbus
2CMC48001M0201
119
A43/A44
Revision: C
User Manual
9.5 Historical Data
General
In the Modbus mapping all historical data is organized as entries. This concerns
Previous values, Demand, Load profile and Event logs.
Entry number 1 is the most recent entry, entry number 2 is the second most recent,
and so on. Entry number 0 is not used.
Readout of all types of historical values is made by writing to a group of registers
called Header and reading from one or more groups of registers called Data
blocks.
The Header is used for controlling readout with respect to date/time or entry
numbers, and for loading new entries into the Data blocks. The data blocks
contain the actual data, for example event log entries or energy values.
When there are no more entries to read all registers in the Data blocks are set to
0xFFFF.
Header registers
There are a number of standard commands that are used in the same way when
reading out any type of historical data. These are represented by registers in the
Header, separately mapped for each functionality, but with the same names.
The following table describes the common header registers:
Get next
entry register
Function
Size Description
Data type
Read/
write
Get next entry
1
Write the value 1 to this register to load
Unsigned
R/W
new values in the Data block(s)
Entry number
1
Write to this register to choose an entry
Unsigned
R/W
number to start reading from
Date/Time
3
Write to this register to choose a date/
Date/Time
R/W
time to start reading from
(see below)
Direction
1
Write to this register to choose the
Unsigned
R/W
direction of reading
The Get next entry register is used to continue an ongoing readout, which was
started by writing to any of the Entry number, Date/Time or Direction registers.
If the direction in Direction register is set to backward the Data block is loaded
with older data. And correspondingly, if the direction is set to forward the Data
block is loaded with more recent data.
Summary of Contents for A43
Page 1: ...A43 A44 User Manual ...
Page 40: ...Meter Settings A43 A44 40 2CMC48001M0201 User Manual Revision C ...
Page 55: ...Technical Description 2CMC48001M0201 55 A43 A44 Revision C User Manual ...
Page 58: ...Technical Description A43 A44 58 2CMC48001M0201 User Manual Revision C ...
Page 61: ...Technical Description 2CMC48001M0201 61 A43 A44 Revision C User Manual ...
Page 75: ...Technical Description 2CMC48001M0201 75 A43 A44 Revision C User Manual ...
Page 84: ...Measurement Methods A43 A44 84 2CMC48001M0201 User Manual Revision C ...
Page 91: ...Measurement Methods 2CMC48001M0201 91 A43 A44 Revision C User Manual ...
Page 95: ...Measurement Methods 2CMC48001M0201 95 A43 A44 Revision C User Manual ...
Page 102: ...Communication with Modbus A43 A44 102 2CMC48001M0201 User Manual Revision C ...
Page 107: ...Communication with Modbus 2CMC48001M0201 107 A43 A44 Revision C User Manual ...
Page 131: ...Communication with Modbus 2CMC48001M0201 131 A43 A44 Revision C User Manual ...
Page 147: ...Communication with Modbus 2CMC48001M0201 147 A43 A44 Revision C User Manual ...
Page 154: ...Communication with Modbus A43 A44 154 2CMC48001M0201 User Manual Revision C ...
Page 157: ...Communication with Modbus 2CMC48001M0201 157 A43 A44 Revision C User Manual ...
Page 161: ...Communication with Modbus 2CMC48001M0201 161 A43 A44 Revision C User Manual ...
Page 166: ...Communication with Modbus A43 A44 166 2CMC48001M0201 User Manual Revision C ...
Page 180: ...Communication with M Bus A43 A44 180 2CMC48001M0201 User Manual Revision C ...
Page 182: ...Communication with M Bus A43 A44 182 2CMC48001M0201 User Manual Revision C ...
Page 188: ...Communication with M Bus A43 A44 188 2CMC48001M0201 User Manual Revision C ...
Page 195: ...Communication with M Bus 2CMC48001M0201 195 A43 A44 Revision C User Manual ...
Page 254: ...Communication with M Bus A43 A44 254 2CMC48001M0201 User Manual Revision C ...
Page 257: ...Communication with M Bus 2CMC48001M0201 257 A43 A44 Revision C User Manual ...