Page 6
Infinity S_Dual V_old_QSG
Version 4.0
© 2021 ABB. All rights reserved.
CAUTION:
Verify battery voltage and polarity with a
voltmeter before connecting.
Lug Landings
Distribution
Battery Bus
Landings
1/4
-
20studs on
5/8”
centers
Lug tongue width
0.68”
max
5/16
-
18 studs on
1”
centers
Torque
65 in
-
lb
-
7/16”
socket
160 in
-
lb
-
1/2”
socket
Optional Battery connection bus adapter—for angled battery cable direction
Bolts to the Battery Return bus and Direct Battery Connection bus bars.
Distribution panels are each equipped with 20
(19”
panel) or 26
(23”
panel) bullet
-
style distribution positions. Each
position is selectable between Primary or Secondary (Converter) Voltage outputs.
Breaker sizes up to 250A, TPS fuses to 70A and GMT fuses to 12A are available.