Information: Rectifier & Converters

 

Rectifier

 

Ordering 

Code

 

Input 

 

DC Output

 

Recommended AC Breaker 

 

3

-

phase

 

Volts

 

amps

 

AC1

 

(2 rectifiers 

per feed)

 

AC3

 

AC5H

 

AC6

 

AC7

 

 

 

NE050ECO48ATEZ 

 

150025074

 

200

-

400Vac

 

48V

 

50A

 

40A

 

20A

 

20A

 

40A

 

20A

 

100

-

120Vac

 

48V

 

22A

 

40A

 

20A

 

20A

 

  

  

60

-

300Vdc, 11A max

 

48V

 

50A

 

  

  

  

  

  

 

 

NE075AC48ATEZ  

 

CC109163473 

 

200

-

277Vac

 

48V

 

75/50A

1

 

40A

 

20A

 

30A

 

50A

 

30A

 

100

-

120Vac

 

48V

 

25A

 

40A

 

20A

 

20A

 

  

  

NE050AC48ATEZ

 

208

-

240Vac

 

48V

 

50A

 

40A

 

20A

 

20A

 

40A

 

20A

 

CC109158878

 

100

-

120Vac

 

48V

 

22A

 

40A

 

20A

 

20A

 

  

  

NE050AC48A 

 

CC109124913

 

200

-

240Vac

 

48V

 

50A

 

40A

 

20A

 

20A

 

40A

 

20A

 

1

 

75A with AC5H, AC6 & AC7 and AC6, 50A with AC1 and AC3.

 

Information: Rectifier Status LEDs

 

Converters 

 

Ordering Code

 

Input DC 

 

Output DC 

 

 

Voltage

 

Current

 

Voltage

 

Current

 

 

NE075DC24A

 

CC109142881

 

48Vdc

 

54A Max

 

24Vdc

 

75A

 

 

NE075DC12AZ

 

150046488

 

48Vdc

 

24A Max

 

12Vdc

 

75A

 

Information: Converter Status LEDs

 

QUICK START GUIDE

 

Summary of Contents for 8600243957P

Page 1: ...e 8600243957P QUICK START GUIDE NES4812 23 AC1 PS4 DC1E LVBD Voltages 48YY 48 Primary YY Secondary 12 or 24 AC input AC1 Molex AC3 IEC 3 20 C 19 AC5 Term Block 19 only AC5H Term Block AC6 3 phase delta Term Block 19 only AC7 3 phase delta wye Term Block 19 only of Power Slots LVBD option of Distribution Panels 1 or 2 19 23 ...

Page 2: ...tions Install service and operate equipment only by professional skilled and qualified personnel who have the necessary knowledge and practical experience with electrical equipment and who understand the hazards that can arise when working on this type of equipment Disconnect batteries from outputs and or follow safety procedures while working on equipment Batteries may be connected in parallel wi...

Page 3: ...é des systèmes de distribution et d alimentation en courant continu y compris les piles et les câbles généralement dans les salles de télécommunication peut affecter les appareils électroniques médicaux tels que les stimulateurs cardiaques Les effets diminuent avec la distance N installez pas cet équipement sur des surfaces combustibles Règles et règlements respectez toutes les règles et réglement...

Page 4: ...If connecting chassis ground to frame surface remove non conductive frame coating and apply antioxidant for connection Tools required Cable Crimpers Torque wrench 0 240 in lb 28 Nm 5 16 7 16 and 1 2 nut drivers Screw Drivers Screw Drivers 1 Flat 2 Phillips Wire cutters and strippers Step 1 Mount the System Mount the system with a minimum gap of 3 inches behind the system to allow proper airflow 1 ...

Page 5: ...tring to the Battery Return bus of the Infinity power system Prepare the cable of each battery string for connection to the Battery HOT bus of the Infinity power system but do NOT connect them at this time Load Connections are made using Load Breakers in the main distribution area AC1 Molex AC3 IEC AC5H TB 23 AC5 TB 19 AC6 TB 19 3ΦDelta AC7 TB 19 3ΦWye Note Battery Cable Connects to the Power Syst...

Page 6: ...s Torque 65 in lb 7 16 socket 160 in lb 1 2 socket Optional Battery connection bus adapter for angled battery cable direction Bolts to the Battery Return bus and Direct Battery Connection bus bars Distribution panels are each equipped with 20 19 panel or 26 23 panel bullet style distribution positions Each position is selectable between Primary or Secondary Converter Voltage outputs Breaker sizes ...

Page 7: ...x 1 Step 5 Set Controller alarm relay jumpers Pulsar Plus Set jumpers 1 thru 10 for the ten alarm relays as Close on Alarm or Open on Alarm Factory default setting is Open on Alarm Protector Alarm Pin up 24V Protector Note Orientation 48V Protector positions Blue Terminals Lower positions 24V Protector positions Orange Terminals Upper positions 48V Protector Note Orientation Protector Alarm Pin up...

Page 8: ... input circuits to the system positions and is equipped with rectifier Verify the positive cables of battery string to battery return bus and negative cables of battery string to Battery HOT bus of the system as shown in step 4 Energize the AC input circuits and slot one rectifier module only Wait for the system controller to energize establishing communication with the slotted rectifier Use a VOM...

Page 9: ...2 10 ft 3X8AWG CC848830522 2 4 ft 3X8AWG CC848773515 15 ft 10AWG SO Cord CC848906586 10 ft 8AWG SO Cord Information AC Cord Options Information Controller Default Voltage Settings Step 9 Configure Controller Verify and edit controller basic configuration parameters per site engineering instructions Refer to Galaxy Pulsar Plus Product Manual for additional information Parameter Range Valve Reg Defa...

Page 10: ...ry On Discharge_C BD_C 14 W W BK R2 Very Low Voltage VLV 5 S BK R2_C Very Low Voltage_C VLV_C 15 W BK W R3 Fuse Alarm Major FAJ 6 BL BL W R3_C Fuse Alarm Major_C FAJ_C 16 R BL R R4 AC Fail ACF 7 O O R R4_C AC Fail_C ACF_C 17 R R R5 Rectifier Fail RFA 8 G G W R5_C Rectifier Fail_C RFA_C 18 R R G R6 Mult Rectifier Fail MRFA 9 BR W R R6_C Mult Rectifier Fail_C MRFA_C 19 R R W R7 High Voltage HV 10 S ...

Page 11: ...een Normal Amber Minor Alarm Red Critical Major Alarm Some alarms may occur during initial installation eg thermal probe fail or Major Minor communication fail Clear these alarms Via Controller Display follow the menu path Menu Control Operation Clear Events or Uninstall Equipment Verify Basic Installation Settings Date Time Battery Type number of strings and float voltage Menu Configuration Syste...

Page 12: ...g a standard ethernet cable Use a standard web browser to access the controller web pages at default IP address 192 168 2 1 Warning Do not connect LAN port to a network when set to Server mode Set the controller LAN port to Client or Static before connecting to the network Static is the factory default setting and the typical setting for most networks Once connected to the controller web server a ...

Page 13: ...AC48ATEZ CC109163473 200 277Vac 48V 75 50A1 40A 20A 30A 50A 30A 100 120Vac 48V 25A 40A 20A 20A NE050AC48ATEZ 208 240Vac 48V 50A 40A 20A 20A 40A 20A CC109158878 100 120Vac 48V 22A 40A 20A 20A NE050AC48A CC109124913 200 240Vac 48V 50A 40A 20A 20A 40A 20A 1 75A with AC5H AC6 AC7 and AC6 50A with AC1 and AC3 Information Rectifier Status LEDs Converters Ordering Code Input DC Output DC Voltage Current ...

Page 14: ...cted to shielded intra building cabling grounded at both ends Grounding Bonding Network Connect to an Isolated Ground Plane Isolated Bonding Network or an Integrated Ground Plane Mesh Bonding Network or Common Bonding Network Installation Environment Install in Network Telecommunication Facilities OSP or where NEC applies Battery return may be either Isolated DC return DC I or Common DC return DC ...

Page 15: ... All rights reserved Version Date Description of the change 3 0 12 27 2021 Updated as per template Updated step 8 and added AC5H AC input 4 0 05 26 2022 Corrected labeling in figure on page 4 Change History excludes grammar clarifications QUICK START GUIDE ...

Page 16: ...chase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior writt...

Reviews: