8
/31
1SBC104001M1701
8
GB
F
1
0.1 ... 40
s
10 ... 180
s
2
M5
4.5 N.m
3
4
M3.5 +
Pozidriv 2
1.5 N.m
Connect the contact block
Reconnecter le bloc de contacts
GB
F
GB
F
Tag the connections and disconnect the contact block
Repérer les connexions, déconnecter le bloc de contacts
GB
F
Remove the contact block
Reassembly in the order reverses operations
Démonter le bloc de contacts
Remontage dans l'ordre inverse des opérations
Set the time delay (0.1 ... 40 s ou 10 ... 180 s)
Régler la temporisation (0.1 ... 40 s ou 10 ... 180 s)
GB
F
Calibres 63 ... 550 A
Remplacement et réglage
des contacts temporisés TP..
Replacement and Setting of the
Timed Auxiliary Contacts TP..
63 ... 550 A Ratings
>> Accessories ............................................................................................................... page 10/1
>> Addition of Timed Auxiliary Contacts ..................................................................... page 10/5
>> Spare Parts ................................................................................................................. page 9/1