6
/26
1SBC104001M1701
6
R0076D
1
I
KA2
KA1
KM
KL
Y1
A1
A2
A1
A2
A1
A2
A1
A2
3/L2
4/T2
KM
14
13
KM
12
11
15
18
15
16
KM
KA2
Re
1/L1
2/T1
7/L4
8/T4
5/L3
6/T3
4
5
7
1
3
2
KA1
/ +
/ –
KM
14
13
KL
A1
A2
2
+
–
R0113D
1
Y1
I
KA1
KM
KL
A1
A2
A1
A2
A1
A2
3/L2
4/T2
KM
14
13
KM
12
11
15
18
15
16
KM
KA2
Re
1/L1
2/T1
7/L4
8/T4
5/L3
6/T3
1
3
2
KA1
9
10
+
–
KA2
A1
A2
GB
F
(1) (2) (3) (4)
(4) (5) (6)
IOR-AME
(a.c.)
IORE-AME
(d.c.)
IOR-MT-AME
(a.c.)
IORE-MT-AME
(d.c.)
IOR-CC-AME
(a.c.)
IORE-CC-AME
(d.c.)
NOR-AME, JOR-AME
(a.c.)
NORE-AME, JORE-AME
(d.c.)
LOR-AME
(a.c.)
LORE-AME
(d.c.)
IORR-AME
IORR-MT-AME
IORR-CC-AME
NORR-AME, JORR-AME
LORR-AME
GB
F
a.c. only
uniquement a.c.
(1) Alimentation
entre
4
et
5
Enclenchement
entre
1
et
3
Déclenchement
entre
1
et
2
(2)
Pour les calibres 315 ... 550
A
la bobine de déclenchement KL est alimentée par un redresseur entre 2 et 14.
(3)
En courant alternatif, la résistance d'économie RE et son contact d'insertion 15-16 ne sont pas montés, la
borne A2 de la bobine KM est alors reliée directement à la borne 5.
Si la tension de commande de la bobine de déclenchement est différente de celle de la bobine d'enclenchement,
supprimer la connexion entre les bornes 5 et 7.
(4)
Pour les contacteurs équipés de bobines dont la tension d'alimentation est supérieure à 250
V
un schéma
spécial doit être utilisé (N° CT...).
(5)
Alimentation
entre
9
et
10
Enclenchement
entre
1
et
3
Déclenchement
entre
1
et
2
(6)
Si la tension de commande de la bobine de déclenchement est différente de celle de la bobine d'enclenchement
un schéma spécial doit être utilisé (N° CT...).
Commande par interrupteur, contacteur avec accrochage mécanique
Raccordement
Schémas
(1) Supply
between
4
and
5
Closing
between
1
and
3
Tripping
between
1
and
2
(2)
For 315 ... 550
A
contactor ratings the tripping coil KL is fed between 2 and 14 via a rectifier.
(3)
For a.c. control supply, the economy resistor RE and the insertion contact 15-16 are not mounted.
The terminal A2 of the coil KM is directly connected with the terminal 5.
If the closing coil voltage and the tripping coil voltage are different remove the strap between terminals
5 and 7.
(4)
For the contactors equipped with coils for control voltage upper to 250
V
use a special wiring diagram (No CT...).
(5)
Supply
between
9
and
10
Closing
between
1
and
3
Tripping
between
1
and
2
(6)
If the closing coil voltage and the tripping coil voltage are different
use a special wiring diagram (No CT...).
Control by switch, mechanically latched contactors
Connecting
Diagrams
Summary of Contents for 266M R Series
Page 1: ...GB F Instruction Handbook R Series Contactors Notice d instructions Contacteurs Série R ...
Page 2: ......
Page 48: ...7 2 1SBC104001M1701 7 GB F Notes Notes ...
Page 110: ...8 62 1SBC104001M1701 8 GB F ...
Page 124: ...10 10 8 1SBC104001M1701 GB F Notes Notes ...
Page 128: ...11 4 1SBC104001M1701 11 GB F Notes Notes ...