Troubleshooting procedure
The troubleshooting table is supposed to be used as a detailed instruction together
with the troubleshooting flowchart.
Note
Action
Open the door of the controller and check the
connections between connectors Q1, Q2 & ad-
apter X2.
Check the connections between
connectors Q1, Q2 & X2.
Tip
For more details, see
Circuit dia-
gram - OmniCore C90XT
.
1
How to open the controller is described in
Opening the robot controller on page 180
.
•
If the connection is OK, proceed with
step
.
•
If there is a problem with the connection,
repair the connection and start over.
Make sure that the controller power supply is
in run-time mode.
Power on the controller. Check the
indicator LED MS on the power
unit.
2
Wait at least 1 min after power-on.
If the LED MS is:
•
Green, proceed with step
•
Flashing red/green: a firmware upgrade
error has occurred. This is not supposed
to happen during runtime mode, proceed
with step
•
Pulsing red: replace the power unit, step
.
•
Not lit or red: The controller does not
have sufficient DC input voltage. Proceed
with step
.
Use a multimeter and insulating gloves.
Measure the 24 V DC input voltage
to the power unit.
•
X5
•
X9
3
The input voltage should be 24 V.
Make sure that connectors X5, X9 are connec-
ted properly on both ends.
•
If the 24 V DC input voltage is normal,
proceed with step
•
If the 24 V DC input voltage is abnormal,
proceed with the next step.
If the connection is OK, proceed with the next
step.
Check connection to the robot sig-
nal exchange proxy.
•
A1.X9 (Power unit) - K2.X4
4
If there is a problem with the connection, repair
the connection and go to step
Use a multimeter and insulating gloves.
Measure the AC output voltage.
xx1900000043
5
The output voltage should be 230 V.
Make sure that connectors X6, X7 are connec-
ted properly on both ends.
•
If the output voltage is normal,
Troubleshooting the power supply on
page 407
, and then
robot signal exchange proxy on page 414
•
If the output voltage is abnormal, pro-
ceed with step
.
Continues on next page
Product manual - OmniCore C90XT
391
3HAC073706-001 Revision: E
© Copyright 2020-2021 ABB. All rights reserved.
7 Troubleshooting
7.3.4 Troubleshooting the power unit
Continued
Summary of Contents for OmniCore C90XT
Page 1: ...ROBOTICS Product manual OmniCore C90XT ...
Page 36: ...This page is intentionally left blank ...
Page 50: ...This page is intentionally left blank ...
Page 360: ...This page is intentionally left blank ...
Page 420: ...This page is intentionally left blank ...
Page 428: ...This page is intentionally left blank ...
Page 452: ...This page is intentionally left blank ...
Page 456: ......
Page 457: ......