Note/Illustration
Action
Screws: Torx, countersunk screw M4x10 (4
pcs)
Insert the HMI signal connector into the
cover from inside the cabinet.
3
xx1900001923
Secure it with the screws.
Connect:
•
TPU (X4) - K2.X9 & X13
4
Secure the cables on HMI signal connect-
or into the clips on the cabinet.
Tip
Use the same position as from removing
the HMI signal connector.
5
xx1900001922
Refit the cover plate.
6
Continues on next page
Product manual - OmniCore C90XT
317
3HAC073706-001 Revision: E
© Copyright 2020-2021 ABB. All rights reserved.
5 Repair
5.3.5 Replacing the HMI signal (FlexPendant) connector
Continued