VCC-X Operator Interface SD
VCC-X SETPOINTS
43
Setpoint Screens #6, #7 & #8 - Flush Mount
Space Sensor Calibrate Slide Adjust
VCCX Spts ID 101
Calibrate Slide Adj
put at Up Pos: XXX
Enter # Shown: XXX
The use of this screen is optional and is not required for the sensor
to function. Once the slide adjust value is con
fi
gured on
Setpoint
Screen #5
, this screen is used to calibrate the slider to accurately
provide that offset adjustment in the up position. The value on line
3 will change when the slider moves. Once the slider is in the up
position, wait for the value on line 3 to stop changing. Once it stops
changing, enter this value on line 4.
VCCX Spts ID 101
Calibrate Slide Adj
at Middle Pos: XXX
Enter # Shown: XXX
This screen is used to calibrate the value for the slider when it is
in the middle position. The value on line 3 will change when the
slider moves. Once the slider is in the middle position, wait for the
value on line 3 to stop changing. Once it stops changing, enter this
value on line 4.
VCCX Spts ID 101
Calibrate Slide Adj
at Down Pos: XXX
Enter # Shown: XXX
This screen is used to calibrate the value for the slider when it is in
the down position. The value on line 3 will change when the slider
moves. Once the slider is in the down position, wait for the value
on line 3 to stop changing. Once it stops changing, enter this value
on line 4.
Setpoint Screen #9 - Space Sensor
Push-Button Override Duration
VCC-X Spts ID:#
Space Sensor Push
Button Override
Duration: 2.0Hr
If the VCC-X has a Space Temperature Sensor installed and it has
the Override Button option, the HVAC unit will initiate Override
Mode any time the Override Button is pressed and held for less than
3 seconds. This puts the unit into Occupied operation. The Push-
Button Override Duration Setpoint allows you to adjust the amount
of time the Override will remain in effect when the Override Button
is pressed. To cancel the Override before the Override Duration
time period expires, press the Override Button for 5 to 10 seconds.
VCC-X Setpoint Screens
If using a Digital Space Sensor, pushing the Override Button mo-
mentarily will initiate the Override Mode.
Description
Minimum
Default
Maximum
Space Sensor
Push-Button
Override Duration
0.0 Hr
2.0 Hr
8.0 Hr
Setpoint Screen #10 - Controlling Sensor High
Alarm Offset
VCC-X Spts ID:#
Controlling Sensor
High Alarm Offset
Setpoint: 30.0
º
F
If the Temperature of the controlling sensor rises above the Occupied
Cooling Setpoint by this amount during the Cooling Mode, the con-
troller will generate a High Control Temp Alarm. The unit must be
con
fi
gured for Space Temperature Control, Return Air Temperature
Control, or as a Single Zone VAV unit for this alarm to be generated.
Description
Minimum
Default
Maximum
Controlling Sensor
High Alarm Offset
0ºF
(0
º
C)
30ºF
(16.6ºC)
50ºF
(27.7ºC)
Setpoint Screen #11 - Controlling Sensor Low
Alarm Offset
VCC-X Spts ID:#
Controlling Sensor
Low Alarm Offset
Setpoint: 30.0
If the Temperature of the controlling sensor falls below the Occupied
Heating Setpoint by this amount during the Heating Mode, the con-
troller will generate a Low Control Temp Alarm. The unit must be
con
fi
gured for Space Temperature Control, Return Air Temperature
Control, or as a Single Zone VAV unit for this alarm to be generated.
Description
Minimum
Default
Maximum
Controlling Sensor
Low Alarm Offset
0ºF
(0
º
C)
30ºF
(16.6ºC)
50º F
(27.7ºC)