WIRING
RSMV-HP Technical Guide
6
RSMV-HP Wiring
The RSMV-HP monitors and controls one refrigeration circuit of
the HVAC unit. The module is designed for R410-A refrigerant.
The RSMV-HP is connected to the VCC-X / VCCX2 Controller.
Up to 4 RSMV-HP’s can be connected, depending on the size of the
system. There are 2 E-BUS Expansion Ports which allow the use of
communicating sensors and the E-BUS Modules.
The RSMV-HP provides 6 analog inputs, 4 binary inputs, 4 relays,
and 2 analog outputs. See
Figure 2, below
for inputs wiring and
Figure 3, page 7
for outputs wiring.
24VAC
GND
Line Voltage
Size Transformer For
Correct Total Load.
RSMV = 18 VA
OE370-26-RSMV-HP
RSM For VFD Compressors -
Heat Pump
SP
GND
+V
BK
RD
WH
HP
GND
+V
BK
RD
WH
SUCTION PRESSURE
SENSOR
HEAD PRESSURE
SENSOR
(BY OTHERS)
TEMP1
TEMP2
COMP STAT 1
COMP STAT 2
BIN1
BIN2
COIL TEMP. 1
SENSOR
TEMP3
TEMP4
TEMP5
GND
GND
GND
COIL TEMP. 2
SENSOR
COIL TEMP. 3
SENSOR
COIL TEMP. 4
SENSOR
LEAVING WATER
TEMP SENSOR
BIN3
COM
+
MODULATING
COMPRESSOR
CONDENSER
SIGNAL
AOUT1
AOUT2
COM
+
COIL TEMP SWITCH / POF
GND
M
ENTER
UP
DOWN
ALARM
MENU
OE370-26-RSMV-HP
REFRIGERANT SYSTEM
MODULE V-HP
AAON No.: V61540
E-BUS
+24 V
A
C
GND
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
CONDENSER
COMP 1
COMP 2
SUCTION
PRESSURE
SENSOR
HEAD
PRESSURE
SENSOR
COIL TEMP
SENSORS
BINARY
INPUTS
ANALOG
OUTPUTS
BLACK
+5 V
+5 V
COIL TEMP 1
COMP STATUS 1
BLACK
COMP SIGNAL
CONDENSER VALVE
WHITE
SP
HP
COIL TEMP 2
COMP
2
STATUS
GND
GND
COIL TEMP 3
OUTSIDE COIL TEMP / POWF
NOT USED
COIL TEMP 4
GND
WHITE
RED
RED
GND
GREEN
GREEN
REVERSING VALVE
COMMON
RELAY OUTPUT
TERMINALS
www.aaon.com
WattMaster Overlay
#
000071 Rev1D
SW
EXP VLV 4
BLACK
BLACK
WHITE
WHITE
RED
RED
GREEN
GREEN
EXP VLV 2
EXP VLV 1
EXP VLV 3
E-BUS
LEAVING WATER TEMP
OPEN
GND
GND
MODBUS
RSMV-HP Inputs Wiring
Figure 2: RSMV-HP Inputs Wiring
Suction Pressure Sensor Wiring
The OE275-01 Suction Pressure Transducer must be wired as shown
in
Figure 2, below
. It is required for all compressorized VCC-X /
VCCX2 applications.
Th
e Suction Pressure Sensors are used to measure suction pressure
at the HVAC unit’s DX evaporator coil suction line. Th
is suction
line pressure is converted to saturated refrigerant temperature.
Th
e saturated refrigerant temperature is used to properly control
the compressors to maintain a given Suction Coil (Saturated)
Temperature Setpoint. In Cooling and Heat Pump mode, the
VCC-X / VCCX2 resets the Suction Coil (Saturated) Temperature
Setpoint to maintain a given supply air temperature setpoint. In
Dehumidifi cation mode, the Suction Coil (Saturated) Temperature
Setpoint is a user confi gurable setpoint that does not reset.