Diagnostic Screens
Diagnostic Screens
Refer to the following map when navigating through the Diagnostic
Screens. From the DIAGNSTC Screen, press
<ENTER>
to scroll
through the screens.
DIAGNSTC
SP-A VLT
X.XX
SUCTION PRESSURE SENSOR VOLTAGE
Displays the current voltage of the Suction Pressure Sensor.
HP-A VLT
X.XX
HEAD PRESSURE SENSOR VOLTAGE
Displays the current voltage of the Head Pressure Sensor.
BIN 1 - BIN 4
ON/OFF
BINARY INPUTS #1 - #4
Displays the current status of each Binary Input.
TMP1-TMP 4 VLT
X.XX
COIL TEMPERATURE SENSORS 1 - 4 VOLTAGES
Displays the current voltage of the Coil Temperature Sensor.
TMP5 VLT
X.XX
LEAVING WATER TEMPERATURE SENSOR 5 VOLTAGE
Displays the current voltage of the 2nd Coil Temperature Sensor.
FORCE MODE
ON/OFF
FORCE MODE
Displays the current status of Force Mode. Values are ON/OFF.
RLY 1-4
ON/OFF
RELAYS 1 - 4 FORCE MODE
Press the
<UP>
and
<DOWN>
buttons to select ON or OFF
for each relay.
If forced on, the following screens will appear: