RSMV-HP Technical Guide
RSMV-HP LCD SCREENS
19
Diagnostic Screens
AOUT-1 V
0.0-10.0
vdc
MODULATING COMPRESSOR FORCE MODE
0.0 to 10.0 = Active Force Mode.
Press the
<UP>
and
<DOWN>
buttons to increase and decrease
the value.
AOUT-2 V
1.0-10.0
vdc
CONDENSER FAN FORCE MODE
1.0 to 10.0 = Active Force Mode.
Press the
<UP>
and
<DOWN>
buttons to increase and decrease
the value.
ENTER TO
EXIT
EXV 1-4 %
#%
EXPANSION VALVES OPEN PERCENTAGE
1.0 to 10.0 = Active Force Mode.
Press the
<UP>
and
<DOWN>
buttons to increase and decrease
the value.
ALARM COUNTS Screens
From the ALARM COUNTS Screen, press
<ENTER>
to scroll
through the screens. Each screen will display the name of the alarm
and how many times the alarm has occurred since you last cleared
the alarms. The only way to clear these alarm counts is by using
Prism 2 and selecting, “Select Alarms to Delete” from the ALARM
button menu. See “Alarm Polling” in the
Prism 2 Technical Guide
for more information.
Address Screen
ADDRESS
1(152)
CURRENT BOARD ADDRESS
Confi gure the address according to which refrigerant circuit
this module represents—1=A, 2=B, 3=C, 4=D
Number in parentheses is E-BUS address.
Module 1’s address is 152, Module 2’s address is 153,
Module 3’s address is 154, Module 4’s address is 155
WDOG CNT
#
PWER CNT
#
WATCH DOG TIMER
Displays the number of times the board has been reset due to watch-
dog timer overfl ow.
POWER LOSS COUNT
Displays the number of times the board has been reset
due to power loss.
EPROM:
HOLD
DOWN
TO
LOAD
DEFAULTS