RSMV-HP Technical Guide
RSMV-HP LCD SCREENS
15
Sensor Status Screens & Setpoint Status Screens
SUPRHT 1-4
XX DEG
CURRENT SUPERHEAT 1 - 4 CALCULATIONS
COIL 1 - 4
XX DEG
CALC CT
XX DEG
SUCTION
XXX PSI
COIL TEMPERATURES 1 - 4 READINGS FROM
TEMPERATURE SENSORS INPUT
CALCULATED COIL TEMPERATURE FROM
SUCTION PRESSURE INPUT
SUCTION PRESSURE READING FROM INPUT
Sensor Status Screens
Refer to the following map when navigating through the Sensor
Status Screens. From the SENSOR STATUS Screen, press
<ENTER>
to scroll through the screens.
SENSOR
STATUS
HEAD
XXX PSI
HEAD PRESSURE READING FROM INPUT
Setpoint Status Screens
Refer to the following map when navigating through the Setpoint
Status Screens. From the SETPOINT STATUS Screen, press
<ENTER>
to scroll through the screens.
SETPOINT
STATUS
HEADPRSP
340 PSI
HEAD PRESSURE SETPOINT
Valid range is 275 to 475 PSI. Default is 340 PSI.
H20 TEMP
XX DEG
H20 TEMPERATURE FROM
LEAVING WATER TEMPERATURE SENSOR INPUT
H20 FLOW
YES/NO
LEAVING WATER INPUT STATUS
SUPERHEAT SETPOINT STATUS
Valid range is 1 to 30 degrees. Default is 15 degrees.
SPRHT SP
15 DEG