37
Maintenance
See back of the manual for maintenance log.
At least once each year, a qualified service
technician must check out the unit. Supply
fans, evaporator coils and air filters must be
inspected monthly.
See Startup section for information on air
flow adjustment.
DX Cooling
Set unit controls to cooling mode of operation
with supply fans on. Check the fans for
correct operating direction, amperage and
voltage. Check compressor operation,
rotation, amperage and voltage to the unit
nameplate (check the amperage on the load
side of the compressor contactor). Check for
24V signal across the reversing valve
terminals.
Condensate Drain Pans
Drain pans will have moisture present and
require periodic cleaning to prevent
microbial growth. Cleaning of the drain pans
will also prevent any possible plugging of the
drain lines and overflow of the pan itself.
Cleaning of the drain pans and inside of the
unit must be done only by qualified
personnel.
Supply Fans
Supply Fan Lubrication
Supply fan motors are permanently
lubricated and require no oiling.
Filter Replacement
Monthly filter inspection is required to
maintain optimum unit efficiency.
It is strongly recommended that filter media
be replaced monthly. See
Optional 4-Sided
Air Filter Rack Set-up
prior to maintenance
of the filter rack.
See
Filter Information
section for reference
to the correct size and quantity of filters.
Improper installation, adjustment,
alteration, service or maintenance can
cause property damage, personal
injury or loss of life. Installation and
service must be performed by a
qualified installer. A copy of this IOM
must be kept with the unit.
Blower wheels must be inspected for
excessive dust build up periodically
and cleaned if required. Excessive
dust build up on blower wheels may
cause an unbalanced state; leading to
vibration and/or component failure.
Damages due to excessive dust build
up will not be covered under factory
warranty.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
CAUTION
WARNING
WARNING
Summary of Contents for ProFit WV Series