36
High Discharge Pressure Alarm
The high discharge pressure alarm will
enable if the high pressure switch opens.
This alarm will disable the compressor but
allow the supply fan to operate.
Low Suction Pressure Alarm
The low suction pressure alarm will enable if
the low pressure switch opens for more than
10 seconds. This alarm will disable the
compressor but allow the supply fan to
operate. If this alarm occurs more than twice
in 2 hours the controller will go into a hard
lock out and require a power cycle to reset.
Removal of the compressor call will not reset
the alarm while in hard lock out.
Summary of Contents for ProFit WV Series
Page 2: ......
Page 45: ...Literature Change History July 2022 First Version ...
Page 46: ......
Page 47: ......