19
3. Water loop systems that have been
disinfected.
Chlorides will result in a premature failure of
the refrigerant-to-water heat exchanger.
Failure of the refrigerant-to-water heat
exchanger as a result of chemical corrosion is
excluded from coverage under AAON
warranties and the heat exchanger
manufacturer warranties.
Failure of the refrigerant-to-water heat
exchanger may allow water to enter the
refrigerant circuit and may cause extensive
damage to the refrigerant circuit components.
Any damage to the equipment as a result of
refrigerant-to-water heat exchanger failure
from chemical corrosion due to the fluid in
the refrigerant-to-water heat exchanger is
excluded from coverage under AAON
warranties and the heat exchanger
manufacturer warranties.
Freezing Water in the Heat Exchanger
This product contains one refrigerant-to-
water heat exchanger. A refrigerant-to-water
heat exchanger contains refrigerant in one
passage and water in another passage. Water
is subject to freezing at 32°F. When water
freezes in a heat exchanger significant forces
are exerted on the components of the heat
exchanger where the water is confined.
Failure of the refrigerant-to-water heat
exchanger due to freezing will allow water to
enter the refrigerant circuit and will cause
extensive damage to the refrigerant circuit
components. Any damage to the equipment
as a result of water freezing in the refrigerant-
to-water heat exchanger is excluded from
coverage under AAON warranties and the
heat exchanger manufacturer warranties.
Unit is capable of operating with Entering
Water Temperatures (EWT) as low as 57°F
during cooling mode without the need for an
automatic flow regulating water valve. If the
EWT is expected to be lower than 57°F or
more stable operation is desired, an automatic
flow regulating water valve must be installed.
OPEN LOOP APPLICATIONS
Cupronickel refrigerant-to-water heat
exchangers are recommended with all
open loop applications. Failure to use
a Cupronickel heat exchanger may
result in premature failure of your
system and possible voiding of the
warranty.
Cleaning the cooling tower or water
loop with harsh chemicals such as
hydrochloric acid (muriatic acid),
chlorine or other chlorides, can
damage the refrigerant-to-water heat
exchanger. Care must be taken to
avoid allowing chemicals to enter the
refrigerant-to-water heat exchanger.
See Appendix A - Heat Exchanger
Corrosion Resistance for more
information.
WARNING
CAUTION
Summary of Contents for ProFit WV Series
Page 2: ......
Page 45: ...Literature Change History July 2022 First Version ...
Page 46: ......
Page 47: ......