13
Receiving Unit
When received, check the unit for damage
that might have occurred in transit. If damage
is found, it must be noted on the carrier’s
freight bill. A request for inspection by
carrier’s agent must be made in writing at
once. Check nameplate to ensure the correct
model sizes and voltages have been received
to match the job requirements.
All units are shrink-wrapped in blue wrap. If
a unit shows up with any other color wrap,
the unit has been opened and it must be
thoroughly checked for damage that
necessitated re-wrapping.
If repairs must be made to damaged goods,
notify the factory before any repair action is
taken in order to protect the warranty. Certain
equipment alteration, repair, and
manipulation of equipment without the
manufacturer’s consent may void the product
warranty. Contact the AAON Warranty
Department for assistance with handling
damaged goods, repairs, and freight claims:
918-382-6450.
Note:
Upon receipt check shipment for items
that ship loose. Consult order and shipment
documentation to identify potential loose-
shipped items.
Figure 1 - Access Panels
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction traffic
and in the proper orientation as marked on the
packaging with all internal packaging in
place. Secure all loose-shipped items.
Direct Expansion (DX) Systems
All systems are factory assembled, leak
tested, charged with R-410A refrigerant, and
run tested.
All systems include air coil, reversing valve,
liquid line filter dryer, thermal expansion
valve (TXV), and compressor.
Always control the unit from the thermostat,
or control panel, never at the main power
supply, except for emergency or complete
shutdown of the unit.
During the cooling season, if the airflow is
reduced due to dirty air filters or any other
reason, the cooling coils can get too cold
which can cause excessive liquid to return to
the compressor. As the liquid concentration
builds up, oil is washed out of the
compressor, leaving it starved for lubrication.
The compressor life will be seriously
shortened by reduced lubrication and the
pumping of excessive amounts of liquid oil
and refrigerant.
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
WARNING