91
Flow Measurement with the valve in the
Wide Open position
Where approximate indication of flow is
acceptable the Flo-Trex valve can be used.
Step 1.
Measure and record the differential
pressure across the valve.
Step 2.
With valve in fully open position,
locate the pressure differential on left hand
side of the Flo-Trex Performance Curve with
Valve in Full Open Position chart and extend
line horizontally across to valve size being
used. Drop line vertically down and read flow
rate from bottom of chart.
Safety glasses should be worn.
Probes should not be left inserted into
fittings for long periods of time as
leakage may result.
CAUTION
Summary of Contents for LZ Series
Page 2: ......
Page 27: ...27 Figure 6 Concrete Pad Mounting with Dimensions Figure 7 LZ Base ...
Page 36: ...36 Figure 17 Typical Flue Vent Piping ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 95: ...95 Flo Trex Cross Section ...