16
17
AstroPure 2000 LCD
To access the user menu (to unlock the display), the user can press the ‘AstroPur’ logo or,
alternatively, press the lock symbol for 2 seconds.
The user menu password is “116”.
Main User Menu
Press the AstroPure logo for 3 seconds.
The language settings can be modified and system information can be viewed
(software version, hardware ID).
After 60 seconds of inactivity, the main screen will automatically ‘lock’, viz. no
changes can be made to any settings, e.g., main standby switch on/off, airflow set
point, lamp on/off, etc.
To modify any setting, the screen needs to be unlocked again.
After 60 seconds of inactivity, the main screen will automatically ‘lock’, viz. no
changes can be made to any settings, e.g., main standby switch on/off, airflow set
point, lamp on/off, etc.
To modify any setting, the screen needs to be unlocked again.
Operation (LCD / PLC Control)
•
Plug in the power plug
•
Set the ON/OFF switch at the back side of the unit to ON.
Set the desired volume flow.
•
Press the standby button to turn on the fan
• To unlock the screen, enter the password “116”
•
Volume flow adjustment:
•
Method (1)
•
Press the flow rate bar to set the initial value. The exact desired speed of the fan
can be set here.
•
Press the plus and minus button. The respective speed increment is set in the
configuration menu.
•
Method (2)
•
Press an area on the flow rate bar. With this option, the speed of the fan is set to
one of the 4 parameter values at a time (25% steps).
•
Information on display:
Service: filters must be changed by qualified personnel
Configuration menu, language and system information
Press the AAF-logo field for 5 seconds to enter the configuration menus.
Enter the password “-1101“.
The controller‘s parameters can be changed here.
Resetting of operating hours
In the configuration menu, these values can be reset by pressing the corresponding button for
5 seconds.
Appropriate flow rate
To achieve best air cleaning results, the air cleaners flow rate must be adjusted to the individual
situation of the designated room.
Following calculation steps provide a basic guide line:
• The volume of the designated room in cubic meters (m³) is calculated by multiplying the room’s
length * width * height in meters: V = L * W * H
• The desired number of room air exchanges per hour (ACH) has to be selected (units: 1 /h). This
number is sometimes also referred to as air exchange rate.
When this value is not preset, the following ACH values represent the currently applied
recommendations:
• Good ventilation:
ACH = 4 1/h
• Excellent ventilation:
ACH = 6 1/h
• Purging of rooms:
ACH = 10 1/h
16
AstroPure 2000 Main menu
-> after 5 s ->