The necessary air flow rate is then determined by multiplying the room’s volume V with the 
desired air exchanges per hour. 

•  Necessary flow rate = V * ACH

Example: 

•  A room has the dimensions of (L * W * H) = 5 m * 8 m * 3 m 

•  The volume is calculated to 5 m * 8 m * 3 m = 120 m³.

•  The desired air exchange rate is ACH = 4 1/h

•  The air cleaner has to deliver 4 1/h * 120 m³ = 480 m³/h.

The table below serves for guidance.

Cleaning of the external surface

Always disconnect the AstoPure Air Cleaner from the power connection when cleaning it. 

The surface of the device can be cleaned with common mild soap based household 
cleaning detergents only.

Disposal

Spent filters should be packed in sealed plastic bags individually and disposed off in 
accordance with local waste regulations.

Decommissioned electric and electronic equipment must be returned to approved collecti-
on points in accordance to the local waste regulations.

Inspection and maintenance per component

The device components and filters must be checked for function and wear at regular 
intervals and serviced, at least after the periods specified below or earlier if necessar

18

Parameter

Symbol

Unit

Example 1

Example 2

Example 3

Example 4

Length

L

m

10

10

10

10

Width

W

m

10

10

10

10

Height

H

m

2

2.5

2.5

2.5

Volume

V

m

3

200

250

250

250

Air exchanges per hour

ACH

1/h

4

4

6

8

Required air volume flow

m

3

/h

800

1.000

1.500

2.000

Inspection Intervals

Pre filter:

months

3

HEPA filter: 

months

3

UV-C Stage

months

3

Maintenance door

months

6

Moving parts

months

6

Fan section

months

6

Entire unit

months

Prior to each use and very 12 months

Replacement Intervals

Pre filter:

months

3

Red Pleat

months

6

RedPleat CF

months

6

HEPA Filter

AstroCel III

months

12

MEGAcel I

months

12

UV-C Stage

hours

9.000

7. Emergency:

If possible, disconnect the AstroPure air purifier from the power 
supply by pulling the plug. If it is not possible to pull out the mains 
plug safely, the power supply must be interrupted by disconnecting it 
from the building circuit (safety switch)

Fire fighting

In the event of a fire, fight it with extinguishing agents approved for electrical 
appliances. Dangerous substances escape in the event of fire.
In the event of a fire, do not breathe the fumes and smoke that may be produced. 
After ensuring that the extinguishing is complete, ensure that the rooms are 
adequately ventilated.

DANGER: 
Electric shock

Summary of Contents for AstroPure 2000

Page 1: ...AstroPure 2000 Air Cleaner IOM AstroPure Installation and Operation Manual...

Page 2: ...transport and assembly 13 Commissioning Operation Cleaning and Disposal 19 Emergency 20 Drawings and diagrams 21 Spare parts 21 Certificates and Protocols 22 Appendix Potentiometer Control Manufacture...

Page 3: ...be trained and instructed for example according to VDI 6022 4 The AstroPure air purifier is shipped with an installation operation and maintenance manual AAF HEPA filter test report For maintenance i...

Page 4: ...switch in OFF Set the speed controller to the OFF position Plug in the power plug ON OFF switch ON Check serial number for fan type on the Type Plate on the back of the uni Serial No E11 2020 12345 E...

Page 5: ...teristics example below Image 1 AstroPure type label 3 Quick Start Guide LCD PLC Control Quick start guide Observe the safety instructions for safe operation Ensure a safe stand on smooth level stable...

Page 6: ...Device weight kg 150 Min ambient temperature C 0 Max ambient temperature C 40 Allowed rel humidity level 0 90 depending on execution Connection details and power consumption Connection details 1PH 23...

Page 7: ...ackaging Storage temperature range 30 C to 40 C Air humidity rH 90 no condensable humidity Unpacking Remove the securing straps stretch wrap and card board packing material from the AstroPure 2000 Air...

Page 8: ...vice is properly closed Make sure that the air inlet and outlet openings are freely accessible and not obstructed or occupied Fix the locking devices of the castors General In case of any abnormal noi...

Page 9: ...be set here Press the plus and minus button The respective speed increment is set in the configuration menu Method 2 Press an area on the flow rate bar With this option the speed of the fan is set to...

Page 10: ...ied below or earlier if necessar 18 Parameter Symbol Unit Example 1 Example 2 Example 3 Example 4 Length L m 10 10 10 10 Width W m 10 10 10 10 Height H m 2 2 5 2 5 2 5 Volume V m3 200 250 250 250 Air...

Page 11: ...enwaldstrasse 4 D 64646 Heppenheim Germany Telefon 49 0 6252 69977 0 Email Sales DACH aafeurope com A risk assessment and compliance evaluation procedure has bend conducted referenced on the following...

Page 12: ...LLED PRODUCT OWNER FM AAF DRAWING NO mm SHEET UL DO NOT SCALE DRAWING REF Material Finishing MATER Roughnes 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 A A B B C C D D E E F F AP2000 LCD Guillaume Fogeron 19 03 2...

Page 13: ...10 663 51 09 E mail greece aafeurope com Italy AAF S r l Via Friuli 28 30 21047 Saronno VA Phone 39 02 9624096 Fax 39 02 9606409 E mail sales italy aafeurope com Dinair Norway Dinair AS Prof Birkeland...

Reviews: