background image

10

GAS SUPPLY SYSTEMS

Low  pressure  building  gas  supply  systems  are  defined  as  those 

systems  that  cannot  under  any  circumstances  exceed  14” W.C. 

(1/2 PSI Gauge). These systems do not require pressure regulation.  

Measurements should be taken to insure that gas pressures are stable 

and fall within the requirements stated on the water heater rating plate. 

readings should be taken with all gas burning equipment off (static 

pressure) and with all gas burning equipment running at maximum rate 

(dynamic pressure). The gas supply pressure must be stable within 1.5” 

W.C. from static to dynamic pressure to provide good performance.   

Pressure drops that exceed 1.5” W.C. may cause rough starting, noisy 

combustion or nuisance outages.  Increases or spikes in static pressure 

during off cycles may cause failure to ignite or in severe cases damage 

to appliance gas valves. If your low pressure system  does  not meet  

these  requirements,  the  installer  is responsible for the corrections.
High  Pressure  building  supply  systems  use  pressures  that exceed 

14” W.C. (1/2 PSI Gauge). These systems must use field supplied 

regulators to lower the gas pressure to less than 14” W.C. (1/2 PSI 

Gauge). Appliances require gas regulators that are properly sized for the 

water heater input and deliver the rating plate specified pressures.  Gas 

supply systems where pressure exceeds 5 PSI often require multiple 

regulators to achieve desired pressures. Systems in excess of 5 PSI 

building pressure should be designed by gas delivery professionals 

for best performance. Water heaters connected to gas supply systems 

that exceed 14” W.C. (1/2 PSI Gauge) at any time must be equipped 

with a gas supply regulator.

GAS PRESSURE REQUIREMENTS                                 

BL-100 natural gas model requires a minimum gas supply pressure of 

5” w.c. (1.25 kPa); BL-80 natural gas model requires a minimum gas 

supply pressure of 6” w.c. (1.49 kPa). The minimum supply pressure 

is  measured  while  gas  is  flowing  (dynamic  pressure). The  supply  

pressure  (dynamic)  should  never  fall  below  the specified minimum 

supply pressure. The supply pressure should be measured with all gas 

fired appliances connected to the common main firing at full capacity. If 

the supply pressure drops more than 1.5” W.C. (0.37 kPa) as gas begins 

to flow to the water heater then the supply gas system including the 

gas line and/or the gas regulator may be restricted or undersized. See 

Supply Gas regulator section and Gas Piping section of this manual. 

The gas valve on all models has a maximum gas supply pressure limit 

of 14” W.C. (3.48 kPa) The maximum supply pressure is measured 

while gas is not flowing (static pressure).

SUPPLY GAS REGULATOR

The  maximum  allowable  gas  supply  pressure  for  this  water heater 

is 14.0 inches W.C. (3.48 kPa). Install a positive lock-up gas pressure 

regulator in the gas supply line if inlet gas pressure can exceed 14.0 

inches W.C. (3.48 kPa) at any time. regulators must be sized/used 

according to manufacturer’s specifications.
If a positive lock-up regulator is required follow these instructions:
1.  Positive lock-up gas pressure regulators must be rated at or above

 

  the input Btu/hr rating of the water heater they supply.
2.  Positive lock-up gas pressure regulator(s) should be installed no

 

  closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters)

 

  of equivalent length from the water heater’s inlet gas connection.
3.  After installing the positive lock-up gas pressure regulator(s) an initial

 

  nominal supply pressure setting of 7.0” W.C. while the  water  heater

 

  is  operating  is  recommended  and  will generally provide good

 

  water heater operation. Some additional adjustment  maybe required

 

  later to maintain a steady gas supply pressure.
4.  When  installing  multiple  water  heaters  in  the  same  gas  supply

 

  system  it  is  recommended  that  individual  positive  lock-up  gas

 

  pressure regulators be installed at each unit.

MIXING VALVES

Water temperature over 125°F (52°C)

can cause severe burns instantly

resulting in severe injury or death.
Children, the elderly and the physically 

or mentally disabled are at highest risk 

for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as

mixing valves must be installed when 

required by codes and to ensure safe 

temperatures at fixtures.

Water heated to a temperature which will satisfy clothes washing, dish 

washing, and other sanitizing needs can scald and cause permanent 

injury upon contact. Short repeated heating cycles caused by small 

hot water uses can cause temperatures at the point of use to exceed 

the water heater’s temperature setting by up to 20°F (11°C).
Some people are more likely to be permanently injured by hot water 

than others. These include the elderly, children, the infirm and the 

physically/mentally disabled. Table 2 shows the approximate time-

to-burn relationship for normal adult skin. If anyone using hot water 

provided  by the  water  heater  being  installed  fits into  one  of these 

groups or if there is a local code or state law requiring a certain water 

temperature at the point of use, then special precautions must be taken.
In  addition  to  using  the  lowest  possible  temperature  setting  that 

satisfies demand of the application a Mixing Valve should be installed 

at the water heater or at hot water taps to further reduce system water 

temperature. See Figure 6.
Mixing  valves  are  available  at  plumbing  supply  stores.  Consult 

a  Qualified  Installer  or  Service  Technician.  Follow  mixing  valve 

manufacturer’s instructions for installation of the valves.

TABLE 2. 

Water 

Temperature °F

 Time for 

1st Degree Burn

(Less Severe Burns)

Time for Permanent Burns

2nd & 3rd Degree

(Most Severe Burns)

110

(normal shower temp.)

116

(pain threshold)

116

35 minutes

45 minutes

122

1 minute

5 minutes

131

5 seconds

25 seconds

140

2 seconds

5 seconds

149

1 second

2 seconds

154

instantaneous

1 second

(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978)

HOT WATER

OUTLET

TO TANK

INLET

CHECK

VALVE

MIXING

VALVE

COLD

WATER

INLET

TEMPERED WATER

OUTLET

12” TO 15”

(30-38 cm)

CHECK

VALVE

FIGURE 6.

INSTALLATION REQUIREMENTS

Summary of Contents for BL-80

Page 1: ...safety messages could result in death or serious injury This manual must remain with the water heater 500 Tennessee Waltz Parkway Ashland City TN 37015 Low Lead Content WARNING If the information in t...

Page 2: ...gs for Confined Spaces 13 Outdoor Air Through Two Openings 13 Outdoor Air Through One Opening 13 Outdoor Air Through Two Horizontal Ducts 14 Outdoor Air Through Two Vertical Ducts 14 Air From Other In...

Page 3: ...hazard what can happen if you do not follow the safety message and how to avoid the risk of injury DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which if not avoide...

Page 4: ...4 GENERAL SAFETY INFORMATION...

Page 5: ...you don t follow the safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation op...

Page 6: ...2 1 1 2 12 1 2 CM 157 6 147 3 74 9 64 1 40 3 10 2 38 7 40 6 5 1 NPT NPT 31 8 Model INPUT RATE F 30 40 50 60 70 80 90 100 110 120 130 140 GPH 246 184 147 123 105 92 82 74 67 61 57 53 C 17 22 28 33 39 4...

Page 7: ...vicing and proper operation of the water heater Installation of water heater must be accomplished in such a manner that if the tank or any connections should leak flow will not cause damage to the str...

Page 8: ...per and inefficient operation of the water heater producing carbon monoxide gas in excess of the safe limits This could result in serious injury or death Contact your local gas supplier for any specif...

Page 9: ...rtain it does not sag thereby obstructing the combustion air flow HARD WATER Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protect...

Page 10: ...manufacturer s specifications If a positive lock up regulator is required follow these instructions 1 Positive lock up gas pressure regulators must be rated at or above the input Btu hr rating of the...

Page 11: ...s not intended for the constant relief of thermal expansion A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion Contact...

Page 12: ...ature Pressure Relief Valve discharge line and 2 the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot If after manually operating th...

Page 13: ...eater and the risk of fire or explosion may result It can also create a risk of asphyxiation LOUVERS AND GRILLES Thefreeareasofthefreshairopeningsintheinstructionsthatfollowdonot takeintoaccountthepre...

Page 14: ...e provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300 mm of the bottom of the enclosure The vertical ducts shall commun...

Page 15: ...er heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation explosion or asphyxiation Align the legs of the draft hood with the holes provided Insert...

Page 16: ...IN INCHES MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR LENGTH IN FEET NOMINAL IRON PIPE SIZES INCHES INPUT IN THOUSANDS BTU HR 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 1...

Page 17: ...allation shown in the Figures 15 and 16 Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion Before attaching the gas line be sure t...

Page 18: ...ter several tries turn the gas control knob clockwise to OFF and call your service technician or gas supplier SEE FIGURE A DANGER Hotter water increases the risk of scald injury Consult the instructio...

Page 19: ...r at the water heater Mixing valves are available at plumbing supply or hardware stores see Figure 6 Follow manufacturer s instructions for installation of the valves Before changing the factory setti...

Page 20: ...See Condensation in this section OPERATIONAL CONDITIONS SMELLY WATER In each water heater there is installed at least one anode rod for corrosion protection of the tank Certain water conditions will c...

Page 21: ...replaced At least once a year a visual inspection should be made of the main burner and pilot burner see Figure 19 Inspect burner fl ames through viewport Flames should be very small with a blue haze...

Page 22: ...ter temperature and usage see chart The higher the water temperature or water usage the more lime deposits are dropped out of the water This is the lime scale which forms in pipes heaters and on cooki...

Page 23: ...drained before opening cleanout To clean heater through cleanout opening proceed as follows 1 Drain heater 2 Remove outer cover plate from lower side of heater jacket 3 Remove six 6 hex head screws se...

Page 24: ...er is no longer hot 4 Close the cold water inlet valve to the water heater 5 Connect a hose to the water heater drain valve and terminate it to an adequate drain 6 Open the water heater drain valve an...

Page 25: ...an condense on the cooler surfaces of the tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold I Wa...

Page 26: ...Gas Control Replace Gas Control PILOT OUTAGE Dirty pilot burner Clean pilot assembly Thermocouple malfunction Replace pilot assembly and or thermocouple Defective Gas Control Replace Gas Control Ther...

Page 27: ...ocal codes shall govern their usage 4 The Tank Temperature Control should be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat s...

Page 28: ...trol should be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Cont...

Page 29: ...Control should be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature C...

Page 30: ...ired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE...

Page 31: ...rature Control should be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temper...

Page 32: ...he pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 2 UNITS TWO TEMPERATU...

Page 33: ...33 NOTES...

Page 34: ...34 NOTES...

Page 35: ...gas type venting connections combustion air voltage wiring or fusing Failure to follow applicable codes Failure to follow printed instructions Improper installation sizing delivery or maintenance Cla...

Page 36: ...36 500 Tennessee Waltz Pkwy Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 www hotwater com Copyright 2014 A O Smith Corporation All rights reserved...

Reviews: