Instruction manual ADMR
73
F04 (lock out error)
Three unsuccessful
ignition attempts.
No gas
1. Open the main gas valve and/or the manual gas valve supplying
the water heater
2. Check the supply pressure to the gas control
3. If necessary, repair the gas supply
To repair the gas supply, contact your installation engineer
Air in the gas pipes
Bleed the air out of the gas pipe
See
Checking the supply pressure and burner pressure
for how to
bleed air from the gas line, and measure the supply pressure and
burner pressure.
No burner pressure
1. Check the burner pressure to the gas control
2. Check that the gas valve(s) open and shut correctly
3. If necessary, replace the gas control.
Defect in the hot
surface igniter circuit
1. Check that the hot surface igniter is correctly connected (JP2).
2. Check the wiring of the hot surface igniter.
3. Measure the resistance across the hot surface igniter. This must
lie between 2 and 5 ohms.
4. Check that the hot surface igniter lights up during ignition.
5. If necessary, replace the hot surface igniter.
If the error persists, contact your installation engineer.
To replace the necessary parts, you must contact your installation
engineer
Defect in the ionisation
circuit
1. Check that the flame probe is correctly connected (JP2)
2. Check the wiring of the flame probe
3. Measure the ionisation current. This must be at least 1.5
microamps.
4. Replace the wiring if necessary.
Supply voltage too low Check the supply voltage, this must be 230 VAC (-15%, +10%).
F05 (lock out error)
Too many flame errors
have been signalled.
Incorrect roof flue
terminal
Recirculating flue
gases.
1. Check that the correct roof flue terminal
(3.9 "Chimney flue")
has been installed.
2. If necessary, install the correct roof or wall conduit.
3. Check that the roof or wall conduit discharges into a permitted
area.
If the error cannot be resolved or is persistent, contact your
installation engineer
Symptom
Cause
Solution
Remark
Summary of Contents for ADMR-115
Page 4: ...4 Instruction manual ADMR gis...
Page 8: ...Table of contents 8 Instruction manual ADMR...
Page 12: ...Introduction 12 Instruction manual ADMR 1 gis...
Page 38: ...Installation 38 Instruction manual ADMR 3 is...
Page 56: ...Shutting down 56 Instruction manual ADMR 10 gis...
Page 64: ...Main menu 64 Instruction manual ADMR 11 gis...
Page 78: ...is Instruction manual ADMR 78...
Page 80: ...Maintenance frequency 80 Instruction manual ADMR 14 is...
Page 86: ...Performing maintenance 86 Instruction manual ADMR 15 s...
Page 94: ...Appendices 94 Instruction manual ADMR 17 is...
Page 96: ...Instruction manual ADMR 96...