Instruction manual ADMR
53
gis
9
Starting and running
9.1
Starting and running
Start the appliance as follows:
1. Fill the appliance
(5 "Filling")
.
2. Open
(3.5 "Installation diagram")
the manual gas
valve.
3. Switch on the power to the appliance using the
isolator between the appliance and the power
supply.
4. Switch the electronic controller
ON
by setting the
ON/OFF switch to
position I
.
The display will now show
INTERNAL CHECK
for
about 10 seconds and go to the main menu.
5. Press the blue arrow once ( ) to position the
cursor in front of
ON
and press
. The
display shown in the figure will appear.
6. Confirm the
START OPERATION
by pressing
.
The appliance is now in "ON mode". If there is a
heat demand, the appliance will run through the
heating cycle
(2.3 "The appliance's heating
cycle")
.
If the heating cycle is not run, there is no heat
demand; if this is the case, Tset will probably need
to be set
(11.3 "Setting the water temperature")
.
9.2
The appliance's heating cycle
The appliance's heating cycle is activated as soon as
the measured water temperature (T
net
) falls below the
threshold value (T
set
). This threshold value depends
on the currently selected appliance operating mode.
For example, if the appliance is in "OFF mode" (frost
protection), then this value is 5°C. If the appliance is in
"ON mode", then this threshold value is selectable, for
example, 65°C.
The heating cycle runs in turn through the following
states:
1. HEAT DEMAND
2. WAITING TIME
3. FLUE DAMPER
4. PRE-GLOW
5. IGNITION
6. RUNNING
7. WAITING TIME
The complete cycle is explained in the following
example, which assumes the appliance is in the basic
mode
ON
.
Note
The same heating cycle applies to the other
operating modes.
Once the appliance starts, it will run through the
following steps:
1. The water temperature drops below the set
temperature of (for example)
65
°C. The electronic
controller detects a demand and starts the heating
cycle.
-
The icon is activated.
-
The message
HEAT DEMAND
appears.
2. Following demand, the waiting time starts. The
waiting time lasts approximately 12 seconds.
-
The icon is activated.
-
The message
WAITING TIME
appears.
INTERNAL CHECK
MENU
»OFF
^ ON
È WEEK PROGRAM
»START OPERATION
^ CHANGE SETPOINT
È
Tset=65ÉC
ON
Ê
13:45 Thursday
63ÉC
Tset 65ÉC
HEAT DEMAND
Summary of Contents for ADMR-115
Page 4: ...4 Instruction manual ADMR gis...
Page 8: ...Table of contents 8 Instruction manual ADMR...
Page 12: ...Introduction 12 Instruction manual ADMR 1 gis...
Page 38: ...Installation 38 Instruction manual ADMR 3 is...
Page 56: ...Shutting down 56 Instruction manual ADMR 10 gis...
Page 64: ...Main menu 64 Instruction manual ADMR 11 gis...
Page 78: ...is Instruction manual ADMR 78...
Page 80: ...Maintenance frequency 80 Instruction manual ADMR 14 is...
Page 86: ...Performing maintenance 86 Instruction manual ADMR 15 s...
Page 94: ...Appendices 94 Instruction manual ADMR 17 is...
Page 96: ...Instruction manual ADMR 96...