Installation
36
Instruction manual ADMR
3
is
The display will now show
INTERNAL CHECK
for about 10 seconds and
go to the main menu.
8. Activate the "ON mode" by going through the following steps:
-
Press the blue arrow once ( ) to position the cursor in front of
ON
and
press
. The display shown here will appear.
-
Confirm the
by pressing
START OPERATION
.
The appliance is now in the "ON mode" and will ignite.
9. When the display shows the text
RUNNING
, you must wait about 1 minute
before reading the dynamic pressures.
10. Use the pressure gauge to read the supply pressure at test nipple (6). Refer
to the gas data table
(3.4.3 "Gas data")
.
Note
Consult the mains gas supply company if the supply pressure is not correct.
11. Use the pressure gauge to read the burner pressure at nipple (8). Refer to
the gas data table
(3.4.3 "Gas data")
.
Note
If the burner pressure is incorrect and the appliance is fitted with a blank
plate or high-low control, then you
cannot adjust
the pressure. In this case,
consult your installation engineer or supplier. If the appliance is indeed fitted
with a burner pressure regulator, the pressure can be adjusted by following the
steps below.
INTERNAL CHECK
MENU
»OFF
^ ON
È WEEK PROGRAM
»START OPERATION
^ CHANGE SETPOINT
È Tset=65ÉC
Summary of Contents for ADMR-115
Page 4: ...4 Instruction manual ADMR gis...
Page 8: ...Table of contents 8 Instruction manual ADMR...
Page 12: ...Introduction 12 Instruction manual ADMR 1 gis...
Page 38: ...Installation 38 Instruction manual ADMR 3 is...
Page 56: ...Shutting down 56 Instruction manual ADMR 10 gis...
Page 64: ...Main menu 64 Instruction manual ADMR 11 gis...
Page 78: ...is Instruction manual ADMR 78...
Page 80: ...Maintenance frequency 80 Instruction manual ADMR 14 is...
Page 86: ...Performing maintenance 86 Instruction manual ADMR 15 s...
Page 94: ...Appendices 94 Instruction manual ADMR 17 is...
Page 96: ...Instruction manual ADMR 96...