Instruction manual ADMR
19
is
3.3.4
Working clearances
For access to the appliance, it is recommended that the following clearances
are observed (see figure):
•
AA: around the appliance's control column and cleaning openings: 100 cm.
•
BB: all sides of the appliance: 50 cm.
•
Above the appliance (room to replace the anodes):
-
100 cm if using fixed anodes, or
-
50 cm if using flexible anodes.
If the available clearance is less than 100 cm, flexible magnesium anodes
may be ordered.
Note
When installing the appliance, be aware that any leakage from the tank
and/or connections can cause damage to the immediate environment or floors
below the level of the boiler room. If this is the case, the appliance should be
installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at least
5cm deep with a length and width at least 5cm greater than the diameter of the
appliance.
Working clearances
B
B
AA
AA
AA
IMD-0262 R2
Summary of Contents for ADMR-115
Page 4: ...4 Instruction manual ADMR gis...
Page 8: ...Table of contents 8 Instruction manual ADMR...
Page 12: ...Introduction 12 Instruction manual ADMR 1 gis...
Page 38: ...Installation 38 Instruction manual ADMR 3 is...
Page 56: ...Shutting down 56 Instruction manual ADMR 10 gis...
Page 64: ...Main menu 64 Instruction manual ADMR 11 gis...
Page 78: ...is Instruction manual ADMR 78...
Page 80: ...Maintenance frequency 80 Instruction manual ADMR 14 is...
Page 86: ...Performing maintenance 86 Instruction manual ADMR 15 s...
Page 94: ...Appendices 94 Instruction manual ADMR 17 is...
Page 96: ...Instruction manual ADMR 96...