A.O. Smith 200 Series Instruction Manual Download Page 15

15

CONVENTIONAL SPACE HEATING INSTALLATION

Modern fin type boilers are exceptionally fast heating units.  The low
water volumes in relation to firing rates require special attention to
water flow rates for smooth, efficient operation.  These
considerations for the A. O. Smith copper heat exchanger boilers
are covered below.

Refer to table 4 showing flow rate vs. pressure drop and temperature
rise.

Figure 10 shows a typical installation of the boiler.

A system with several flow controlled zones, or with a 3-way mixing
valve system could present a flow rate to the boiler of less than
required for a maximum of 50°F (28°C)  temperature rise.  Design
system with compensating bypasses to the boiler.

A system bypass should be installed as shown in figure 10 to
prevent boiler circulation starvation when the system zones call for
reduced flow.

This bypass may also be used with multiple boilers manifolded for
reverse-return flow.  The system bypass would be installed from
boiler outlet to suction side of pump.

The boiler piping system of a hot water heating boiler connected to
heating coils located in air handling units where they may be
exposed to circulating refrigerated air, must be equipped with flow
control valves or other automatic means to prevent gravity circulation
of the boiler water during the cooling cycle.   It is highly recommended
that the piping be insulated.

INSTALLATION AS BOILER REPLACEMENT

Installation as boiler replacement on an old system with large water
volume may result in condensation within the boiler on cold starts.
This condensing of water vapor in the combustion area can be
prevented if a portion of the system water flow is diverted past the
boiler to cause an increase in boiler temperature rise.

BYPASS BALANCING

With systems where water temperature can be expected to drop
appreciably due to long standby periods, or heavy draw down, a
bypass pipe of at least 1" size with a balancing cock should be
installed between the boiler inlet and outlet (see figure 10).  When
the system first starts, the valve should be slowly opened until the
condensing ceases.  This adjustment remains at a permanent
setting to establish required temperature rise across the boiler.

AIR SEPARATOR

An air separator as shown in the piping diagram is reccommended
especially for modern commercial hydronic systems.

VENT VALVES

It is recommended that automatic, loose key or screwdriver type
vent valves be installed at each convector or radiator.

SYSTEM HEADERS

Split systems with individual supply and return lines from the boiler
room should normally have this piping connected to supply and
return manifold headers near the boiler.  To achieve good water
distribution with minimum pressure drop for several circuits,
manifolds should be larger than system loops.

SYSTEM INSTALLATION

GENERAL

If the system is to be filled with water for testing or other purposes
during cold weather and before actual operation, care must be
taken to prevent a down draft entering the boiler or freezing air from
contacting the system.  Failure to do so may cause the water in the
system to freeze with resulting damage to the system.  Damage
due to freezing is not covered by the warranty.

Good practice requires that all piping, etc., be properly supported.

The boilers described in this manual may be used for space
(hydronic) heating or for the heating of potable water.  If the heater
is to be used for hydronic space heating, follow the instructions on
pages 15-17 given for equipment required for installation as in
Figure 10.  However, if units are to be used for heating potable
water, the information describing specific systems is found on
pages 17-19.  See figures 11 and 13.  Installations must comply
with all local codes.

HYDRONIC INSTALLATION

The following is a brief description of the equipment required for
installations noted in this manual.  All installations must comply
with local codes (see figure 10).

Table 12:  INSTALLATION ITEMS

NO.

SUGGESTED ITEMS FOR INSTALLATION

  1.

PAIR OF SHORT PIPE NIPPLES, PAIR OF BOILER
LOOP TEES AND BALL VALVE BETWEEN SYSTEM
SUPPLY

AND RETURN - ONE SET PER EACH BOILER

  2.

BOILER PIPE LOOP (See Sizing Data Table 4.)

  3.

BOILER CIRCULATING PUMP (See Sizing Data Table 4.)

  4.

THERMOMETER

  5.

PRESSURE GAUGE

  6.

LOW WATER CUTOFF (If Required By Local Code.)

  7.

SAFETY FLOW SWITCH (Factory-Installed)

  8.

RELIEF VALVE (Factory-Installed)

  9.

BOILER INLET - OUTLET

10.

SYSTEM SUPPLY TEMPERATURE THERMOMETER

11.

DRAIN or BLOW-DOWN VALVE

WATER SUPPLY LINE

These boilers can be used ONLY in a forced circulation hot water
heating system.  The pump must be interlocked with the boiler to
prevent boiler operation without water circulation.  See maximum
and minimum flow rate information.  Since most forced circulation
systems will be of the closed type, install the water supply line as
shown on piping diagram, figure 10.  

Severe damage will occur if

the boiler is operated without proper water flow circulation.

Fast filling of large pipe, old radiator installations (where high
pressures are not available) requires bypassing of the pressure
reducing valve.  Generally, pressure purging is not possible with a
well pump system.  High point air venting is essential.  For details,
refer to OPERATION section of this manual on page 22.

If the system is of the open type, a pressure reducing valve will not
be required as the water supply to the system will be controlled by
a manually operated valve.  An overhead surge tank is required.  A
MINIMUM PRESSURE OF 15 PSI (100 kPa) MUST BE MAINTAINED
ON THE BOILER AT ALL TIMES to avoid potential damage to the
boiler that may not be covered by the warranty.

Summary of Contents for 200 Series

Page 1: ...installation and or operation of this boiler Please pay particular attention to the important safety and operating instructions as well as the WARNINGS and CAUTIONS CONTENTS PAGE ROUGH INDIMENSIONS CA...

Page 2: ...Type of Gas Inches W C kPa Volts Hz Amperes GW GB 1000 thru 2500 NATURAL 3 5 0 87 120 60 30 GW GB 1000 thru 2500 PROPANE 10 2 49 120 60 30 All Models Maximum Supply Pressure 14 0 In W C 3 49 kPa Mini...

Page 3: ...2 27 7 33 3 38 8 44 4 50 55 5 61 1 66 7 72 2 GW 1000 990 000 290 1 LPH 9526 7620 6350 5443 4763 4234 3810 3462 3175 2930 GPH 2520 2016 1680 1440 1260 1120 1008 916 840 775 GW 1300 1 300 000 380 9 LPH...

Page 4: ...d by a rate of 4 for each 1 000 feet 300 m above sea level FOREWORD These designs comply with the latest edition of the American National Standards for Gas Fired Low Pressure Steam and Hot Water Boile...

Page 5: ...ignition trials the boiler will lock out Upon lockout manually push the ENTER RESET button on the display panel to restart the boiler WATER FLOW SWITCH The Water Flow Switch is installed at the boiler...

Page 6: ...SUCH THAT IT NATURALLY DRAINS ITSELF If any safety relief valve is replaced the replacement valve must comply with the latest version of the ASME Boiler and Pressure Vessel Code Section IV HEATING BO...

Page 7: ...waxes and process chemicals are typical compounds which are corrosive These materials are corrosive at very low concentration levels with little or no odor to reveal their presence Products of this s...

Page 8: ...1 square inch per 14 000 BTU in excess of 1 000 000 BTUH This opening s shall be located at or ducted to a point neither more than 18 46 0 cm nor less than 6 inches 15 2 cm above the floor level Where...

Page 9: ...he combustion process horizontal terminations must not be located over areas of pedestrian or vehicular traffic i e public walkways or over areas where condensate could create a nuisance or hazard Thi...

Page 10: ...ortion of the vent shall be supported to maintain clearances and to prevent physical damage or separation of joints TABLE 7 STANDARD VERTICAL VENTING CATEGORY I Extending venting over 70 feet 21 3 m m...

Page 11: ...special gas vent pipes listed for use with Category III gas burning heaters such as stainless steel Saf T Vent by Heat Fab Inc available from A O Smith WPC 5621 W 115th Street Alsip IL 60803 Phone 1 8...

Page 12: ...boiler to the vent terminal The horizontal portion of the vent shall be supported to maintain clearances and to prevent physical damage or separation of joints Figure 7 APPLIANCE CERTIFIED EXHAUSTVENT...

Page 13: ...800 433 2515 Pipe joints must be positively sealed TABLE 10 DIRECT VENT HORIZONTAL EXHAUST CONFIGURATIONS Figure 8 APPLIANCE CERTIFIED VENT MAXIMUM AIRINTAKE AIRINLET MAXIMUM MODEL CATEGORY EXHAUSTVEN...

Page 14: ...he Installed vent be airtight Please insure that all joints are sealed properly during installation DIRECTVENTVERTICALANDHORIZONTALVENTING For direct vent applications this boiler may be vented accord...

Page 15: ...minimum pressure drop for several circuits manifolds should be larger than system loops SYSTEM INSTALLATION GENERAL If the system is to be filled with water for testing or other purposes during cold w...

Page 16: ...g that is desired A single boiler installation might be controlled directly from space temperature thermostat s Multiple boiler installations are more effective when the boilers are sequenced in and o...

Page 17: ...ance loop must be installed see figures 11 and 13 HARD WATER CONDITIONS Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protect the...

Page 18: ...l tank IMPORTANT SAFETY FLOW SWITCH PROTECTS THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR CIRCULATOR FAILURE PIPE TO OPEN DRAIN X FACTORY INSTALLED ON UNIT SUPPLIED WITH UNIT FIELD INSTALLED IN...

Page 19: ...ED DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATUREAT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 23 IF HIGHER PREHEAT TEM PERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTE...

Page 20: ...92 2 841 2 577 2 372 2 197 2 109 1 962 1 757 1 611 1 464 1 347 Length of Pipe in Feet Metres Nominal Iron Pipe Size Cap 10 Ft 20 Ft 30 Ft 40 Ft 50 Ft 60 Ft 70 Ft 80 Ft 90 Ft 100 Ft 125 Ft 150 Ft 175 F...

Page 21: ...ted Rating Input Number of Model BTUH Burners Natural Holes Propane Holes GB GW 1000 990 000 10 0 111 4X 0 071 3X GB GW 1300 1 300 000 13 0 111 4X 0 071 3X GB GW 1500 1 500 000 15 0 111 4X 0 071 3X GB...

Page 22: ...th a 10 amp fuse located inside the control box Note Four extra 3 amp fuses and one 5 amp fuse are supplied with the boiler Recommended Replacement fuses 3 Amp Littlefuse automotive fuse PN 257003 5 A...

Page 23: ...ssure should read 10 W C IMPORTANT UNDER NO CIRCUMSTANCES SHALL THE GAS PRESSURE MEASUREDATTHE BURNER MANIFOLD EXCEED THAT STATED ON THE BOILER RATING PLATE OVERFIRING WILL RESULT IN DAMAGE TO THE BOI...

Page 24: ...5 MINUTES TO CLEAR OUTANYGAS THEN SMELLFORGAS INCLUDINGNEARTHEFLOOR IFYOU SMELLGAS 1 SET THE SYSTEM CONTROLLER TO THE LOWEST SETTING 2 TURN POWER SWITCH ON APPLIANCE TO OFF POSITION 3 REMOVEACCESS PAN...

Page 25: ...FIEDSERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACEANYPARTOFTHECONTROLSYSTEMANDANY GASCONTROLWHICHHASBEENUNDERWATER E DO NOT OPERATE APPLIANCE UNLESS UNIT IS FILLED WITH WATERAND WATER LINE...

Page 26: ...TER RESET enable the user to adjust set points differentials post circulate time reset the cycle count and reset the control system during lock out Changes made to programmable features are stored in...

Page 27: ...rature Set point Value Set Appliance Stage Switching Differential Value Select Appliance Post Circulate Time Check Appliance Cycle Count View Last Error Encountered by Control Control the water temper...

Page 28: ...n on the display screen when the OUTLET LED is illuminated The red wires control the ECO Emergency Cutoff which shuts down the unit if the water temperature exceeds 250 F 121 C and requires a manual r...

Page 29: ...see the section labeled Procedure for Setting Stage Differential Procedure for Setting Stage Differential Once the system control and set point temperature has been entered the switching differentials...

Page 30: ...set the cycle count to zero press the ADJUST push button Press the ENTER RESET push button to successfully reset the cycle count If the ENTER push button is not pressed the reset function will not be...

Page 31: ...excessive lifting of flame from burner ports see Figure 17 If the preceding burner characteristics are not evident check for accumulation of lint or other foreign material that restricts or blocks the...

Page 32: ...rviceman should follow this procedure when the boiler s intake and exhaust piping need cleaning 1 Turn off the electrical power and manual gas shut off Allow boiler parts to cool before disassembly 2...

Page 33: ...16 red fault LED indicators to help pinpoint the source of failures In addition the display will inform the user on which stage the failure occurred by illuminating a red Stage LED In cases where the...

Page 34: ...RD STAGE 3 013 HARD STAGE 4 014 HARD LWCO 020 HARD CIRCULATE FAULT FLOW SWITCH 030 SOFT INSUFFICIENT AIR AIR PRESSURE SWITCH STAGE 1 041 SOFT STAGE 2 042 SOFT STAGE 3 043 SOFT STAGE 4 044 SOFT BLOCKED...

Page 35: ...ties including any warranty of merchantability imposed on the sale of this boiler under state law are limited to one 1 year duration for the boiler or any of its parts Some states or provinces do not...

Page 36: ...36 REPLACEMENT PARTS 5621 W 115TH STREET ALSIP IL 60803 Phone 800 433 2545 Fax 800 433 2515 www hotwater com E Mail parts hotwater com...

Reviews: