Instruction manual BFC
31
is
Water heater with concentric flue gas discharge material
According to the table, the maximum length allowed is 40 metres, and there may
be up to seven 90 degree bends. Both requirements are fulfilled.
Specifications
Caution
For type C13 and C33 installations,A.O.Smith prescribes the use of a roof
or wall flue terminal, exclusively of a type approved for the water heater. Use of
an incorrect roof or wall-mounted flue terminal can cause the installation to
malfunction.
Concentric wall flue terminal specifications C13
IMD-0791 R0
Subject
Description
Wall flue terminal set:
•
1x
w
all flue terminal (incl. wall
flange & clamping ring)
•
1x
p
ipe 500 mm
•
1x 90
o
bend
Art. No.
BFC 28, 30, 50, 60
0302 504
1
BFC 80, 100, 120
0302 326
1
Manufacturer
Muelink & Grol
Type
M2000 MDV SEC
Pipe material
Construction
Concentric
Flue gas discharge
Thick-walled aluminium with lipped sealing ring.
Air supply
Thin-walled galvanised sheet steel.
Pipe diameters
Flue gas discharge
BFC 28, 30, 50, 60
Ø 100 mm
BFC 80, 100, 120
Ø 130mm
Air supply
BFC 28, 30, 50, 60
Ø 150 mm
BFC 80, 100, 120
Ø 200 mm
(1)
No other wall flue terminal is permitted. Use this item number to order the wall conduit set from
supplier,
manufacturer or wholesaler.
Summary of Contents for 120 through 250 Series
Page 4: ...E2 ...
Page 6: ...4 Instruction manual BFC gis ...
Page 10: ...Contents 8 Instruction manual BFC ...
Page 31: ...Instruction manual BFC 29 is Installation types IMD 0789 R0 C43 C13 C53 B23 C33 ...
Page 48: ...Conversion to a different gas category 46 Instruction manual BFC 4 is ...
Page 58: ...Status of the water heater 56 Instruction manual BFC 8 gis ...
Page 62: ...Shutting down 60 Instruction manual BFC 10 gis ...
Page 74: ...Service program 72 Instruction manual BFC 12 is ...
Page 88: ...Service interval 86 Instruction manual BFC 14 is ...
Page 97: ...Instruction manual BFC 95 is ...
Page 102: ...Instruction manual BFC 100 ...